14
Sizing Between Single or 2
nd
Stage Regulator and Appliance*
Maximum propane capacities listed are based on
¹⁄₂
" W.C. pressure drop at 11" W.C. setting. Capacities in 1,000 Btu/h.
Data in accordance with NFPA pamphlet Number 54.
Start-up, Adjustments and Checks
Heating Start-up
This unit is equipped with an electronic ignition device to
automatically light the main burners. It also has a power vent
blower to exhaust combustion products.
On new installations, or if a major component has been replaced,
the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If
any sparking, odors or unusual sounds are encountered, turn off
electrical power and recheck for wiring errors or obstructions in
or near the blower motors. Duct covers must be removed before
operating unit.
Heat Anticipator Setting
Set the heat anticipator on the room thermostat to 0.4 amps to
obtain the proper number of heating cycles per hour and to
prevent the room temperature from overshooting the room
thermostat setting.
Rollout Protection Control
The rollout protection device opens, cutting power to the gas
control valve, if the flames from the burners are not properly
drawn into the heat exchanger. The rollout protection device is
located on the burner bracket. The reason for elevated
temperatures at the control should be determined and repaired
prior to resetting this manual reset control.
Rollout Protection on Burner Bracket
Propane Gas Piping Chart II
Tubing Size, O.D. Type L
Nominal Pipe Size Schedule 40
Pipe or Tubing Length—ft (m)
³⁄₈
"
¹⁄₂
"
⁵⁄₈
"
³⁄₄
"
⁷⁄₈
"
¹⁄₂
"
³⁄₄
"
1"
1
¹⁄₄
"
1
¹⁄₂
"
10 (3)
49
110
206
348
539
291
608
1,146
2,353
3,525
20 (6.1)
34
76
141
239
368
200
418
788
1,617
2,423
30 (9.2)
27
61
114
192
296
161
336
632
1,299
1,946
40 (12.2)
23
52
97
164
253
137
284
541
1,111
1,665
50 (15.2)
20
46
86
146
224
122
255
480
985
1,476
60 (18.3)
19
42
78
132
203
110
231
436
892
1,337
80 (24.4)
16
36
67
113
174
94
198
372
764
1,144
100 (30.5)
14
32
59
100
154
84
175
330
677
1,014
125 (38.1)
12
28
52
89
137
74
155
292
600
899
150 (45.7)
11
26
48
80
124
67
141
265
544
815
200 (61)
10
22
41
69
106
58
120
227
465
697
250 (76.2)
9
19
36
61
94
51
107
201
412
618
300
8
18
33
55
85
46
97
182
374
560
350
7
16
30
51
78
43
89
167
344
515
400
7
15
28
47
73
40
83
156
320
479
Goodman 102
To prevent property damage or serious personal injury
due to fire or explosion caused by a propane gas leak,
install a gas detecting warning device.
If the propane gas unit is installed in an excavated area
or a confined space, a warning device is required due to:
-Propane gas is heavier than air and any leaking gas
can settle in any low areas or confined spaces.
-Propane gas odorant may fade, making the gas
undetectable except with a warning device.
WARNING
A. Rollout protection
Goodman 94
To avoid property damage, personal injury or death due
to fire or explosion, a qualified servicer must investigate
the reason for the rollout protection device to open
before manually resetting the rollout protection device.
WARNING
A