The model selection recommend table for air switch and power cable
1. The power cable used in the unit is copper cable, the working temperature should not exceed the
specified value.
2. If the power cable is longer than 15 meters, please enlarge the cross section of power cable-adequately,
in order to avoid the accident due to overload.
•
Requirement for ground
• Air conditioner is the I class electric appliance, thus please do conduct reliable grounding measure.
• The yellow-green two-color wiring of air conditioner is grounding wire and can not be used for other
purposes. It cannot be cut off and be fixed by screw, otherwise it would cause electric shock.
• The user must offer the reliable grounding terminal. Please don't connect the grounding wire to the
following places:
1. Water pipe;
2. Gas pipe;
3. Blowing pipe;
4. Other places that professional personnel consider them unreliable.
The power cable, communication wire connection between indoor and outdoor
Model
Power supply
Power source cable size
(mm
2
)
Transmition cable size
(mm
2
)
AMD 385
220~240 V, 1PH, 50Hz
3 x 2.5
4 x 0.75
AMD 386
380~415 V, 3PH, 50Hz
5 x 2.5
4 x 0.75