Page 2: ...3 ENGLISH Instructions for use Page 4 FRANÇAIS Mode d emploi Page 43 ESPAÑOL Instrucciones para el uso Página 82 ITALIANO Istruzioni per l uso Pagina 121 AMD 385 386 ...

Page 3: ...Do not repair the air conditioner yourself Incorrect repairs could cause electrocution or fire Contact the Whirlpool Authorized Service Centre nearest you for repairs Never reach with your finger or a stick into the indoor or outdoor unit Never blow the air directly at pets or plants as this may harm them Never spray water onto the unit or wash the air conditioner with water Never let the air cond...

Page 4: ... flow flap at air outlet 4 Refrigerant piping connection electric wire 5 Remote control 6 Air intake grille 7 The built in air filter removes dust and dirt 8 Air outlet AMD 385 386 Indoor Unit AMD 385 Outdoor Unit AMD 386 Outdoor Unit 1 Refrigerant pipe 2 Air outlet 3 Air intake 1 Refrigerant pipe 2 Air outlet 3 Air intake 4 Air outlet ...

Page 5: ...y switch The filter clean is resetted if press the switch DISPLAY PANEL Defrost indicator It lights on during the defrost It lights off when defrost finishes Filter clean It lights on when the filter should be cleaned Timer indicator It lights on when timer is in use It lights off when timer finishes Signal receiving section Receives signal from the remote control Wire remote control is optional a...

Page 6: ...ce where there is water leakage Avoid bumping throwing tossing or frequently opening the wire controller ROOM TEMP C Wireless remoter receiver ON OFF button MODE select button TIMER SLEEP button LCD screen Room temperature sensor FAN speed LOUVER button TEMP setting button ...

Page 7: ...ture suitable providing the soft air flow HEATING mode The air conditioner makes the room warm AUTO RUN mode The air conditioner runs in right mode according to the temperature of room This mode is invalid for AMD 385 5 TIMER SLEEP button Press this button to active sleep mode and will appear in LCD Press again to cancel sleep function Press this button for 3 seconds to active timer function Press...

Page 8: ...85 Fan speed setting auto fan high fan speed middle fan speed low fan speed Temperature display Room temperature Setting temperature SET TEMP C ROOM TEMP C AUTO A timer on timer off timer clock auto fan high fan speed middle fan speed low fan speed Flap direction display swing sign OPERATION WITH WIRE REMOTE CONTROL Mode fuction 1 Press MODE button to select operation mode COOLING mode DEHUMIDIFIC...

Page 9: ...gain to active the timer TIMER OFF flag will stop twinkle and timer begin to work 4 If you need to cancel TIMER OFF press TIMER SLEEP button for 3 seconds to active the timer press button set time 00 00 cancel TIMER OFF after 5 seconds automatically TIMER ON mode 1 You can set timer on when indoor unit is shut off By press TIMER SLEEP button for 3 second timer clock appear on LCD and TIMER ON flag...

Page 10: ...ore please keep the remote control in a location where it can transmit the signal to the indoor unit properly Press once to set and press again to cancel 10 TIMER ON CLOCK BUTTON Used to set the current time Used to set or cancel the timer on operation 11 TIMER OFF BUTTON Used to set or cancel the timer off operation 12 JET BUTTON Used to start or stop the fast cooling 13 DIM BUTTON Used to turn o...

Page 11: ...automatically FAN button is ineffective in this case 3 Setting temperature Press once to raise temperature setting by 1 raise C Press once to lower temperature setting by 1 lower C Note Heating mode is NOT available for cooling only models 4 Turning on Press button when the appliance receives the signal the RUNNING indicator of the indoor unit lights up During mode changes wait a few seconds and r...

Page 12: ...to set the flow angles Swinging airflow Pressing SWING button once the louver will swing up and down automatically Desired direction airflow Pressing the SWING button again when the louvers swing to a suitable angle as desired Note A Do not turn the louvers manually otherwise malfunction may occur If that happens turn off the unit first and cut off the power supply then restore power supply again ...

Page 13: ...e of up to 7 C can be set with the remote control if you still feel uncomfortable What you can do in 6th sense mode Indoor temperature Operation mode Setting temperature Below ST 3 HEATING ST ST 3 to ST 3 FAN ONLY ST Over ST 3 COOLING ST Your feeling button adjustment procedure Uncomfortable because of unsuitable air flow volume Indoor fan speed alternates among High Medium and Low each time this ...

Page 14: ...de JET mode is used to start or stop fast cooling or Heating Fast cooling operates at high fan speed changing the set temperature automatically to 18 C Fast heating operates at auto fan speed changing the set temperature automatically to 32 C In JET mode you can set airflow direction or timer If you want to quit from JET mode press any JET MODE FAN ON OFF or TEMPERATURE SETTING button the display ...

Page 15: ...s to increase or decrease the time setting by 10 minutes Press the or button for a longer time to increase or decrease the time by 1 hour Note If you don t see the time in 10 seconds after you press TIMER ON CLOCK button the remote control will exit the TIMER ON mode automatically ii When your desired time displayed on LCD press the TIMER ON CLOCK button and confirm it A beep can be heard ON stops...

Page 16: ...t and the appliance will operate according to this temperature to let you feel more comfortable Please keep the remote control in a location where it can transmit the signal to the indoor unit properly Press once to set and press again to cancel DIM function Press this button to turn on or turn off display light on indoor unit control panel ...

Page 17: ...ing the batteries do not use new batteries with old batteries or different types of batteries as this may cause the remote control to malfunction If you do not expect to use the remote control for some time take the batteries out to prevent leakage of battery acid in the remote control Operate the remote control within effective range Keep the remote control at least 1 meter from any TV set or HI ...

Page 18: ...he unit Features of COOLING mode Anti freezing When the temperature of the indoor heat exchanger drops to 0 or below compressor will stop working to protect the appliance Features of HEATING mode Preheating In order to prevent cool air blowing 2 5 minutes are necessary to preheat the indoor unit at HEATING operation start The indoor fan will not work during preheating Defrosting In HEATING operati...

Page 19: ...n the filter when the light of Filter turn on Step 2 Cancel the setting Press Emergency switch to return to the standard state 2 Take out the filter Step 1 Open the suction grille after pushing the two knobs as shown by the arrow mark Take out the air filter according the following steps Step 2 Take out the air filter from the suction grille by supporting the air grille and lifting the air filter ...

Page 20: ...use soft brush and neutral detergent Shake off water and dry in a shady place Note Do not wash with hot water 5 Fix the suction grille Refer to step 2 6 Fix the air filter See step 4 How to clean the air filter 7 Close the suction grille Refer to step 1 BEFORE STARTING THE AIR CONDITIONER FOR THE FIRST TIME IN THE SEASON 1 Check to make sure no object obstructing the intake and outlets parts on bo...

Page 21: ...the indoor temperature and humidity decrease You may hear a slight crack when the air conditioner is started or stopped This is the sound of friction caused by expansion of the front panel or other parts due to the change of temperature Air conditioner does not run Is there a power failure Is the power plug loose in the socket Has the circuit protection device been tripped Is the voltage too high ...

Page 22: ...irements for Installation Installation in the following places may cause failure of the air conditioning unit Please contact Whirlpool installation and service agency if the installation in such places cannot be avoided Environments with heat steam flammable or explosive gases or volatile solvents in the air Near high frequency facilities e g welding machines medical equipment Region with high sal...

Page 23: ...professionals The appliance must be fitted with electrical leakage protection switch and an air switch with sufficient capacity Refer to the following chart The air switch must also have a magnetic and a thermal tripping function to ensure protection in case of short circuit and overload 4 Make sure that the power supply cord is long enough to allow the right connection Do not use any extension co...

Page 24: ... the indoor unit and ground is above 2 5 m 7 When installing the suspender bolt check if the install place can stand the weight 4 times of the unit s If not reinforce before installation Refer to the install cardboard and find where should be reinforced Note There will be lots of lampblack and dust stick on the centric fan heat exchanger and water pump in dining room and kitchen which would reduce...

Page 25: ...t D Dimension of ceiling opening and location of the hoisting screw The drilling of holes in the ceiling must be done by the professional personnel Notes The dimension for the ceiling openings with marks can be as large as 910 mm But the overlapping sections of the ceiling and the decorated surface boards should be maintained at no less than 20 mm Dimension of opening 860 to 910 840 Unit size 760 ...

Page 26: ...d in the indoor unit check if 4 angle of every unit are horizontal by water lever If the unit is slant toward the opposite of the coagulate water flow there may be malfunction of the bobber switch and lead water drop Note Please do tighten the nuts and bolts to prevent air conditioner break off 102 Suspension bolts field supplied Nut field supplied Washer with insulation accessary Suspension black...

Page 27: ...f flange 10 to 35 10 to 35 10 to 35 10 to 35 Slub Surface of ceiling Indoor unit Attach the scale to the bottom side of the unit Attach the scale to the face of ceiling Checking scale for dimension of opening Check the dimension of opening at each side Adjust the height of the ceiling and the unit at each corner Pattern paper for installation Dimension for opening Dimension for opening Suspension ...

Page 28: ...de and outside of the flare nut with freeze motor oil screw it by hand and then tighten it with spanner Refer to form 1 to check if the wrench had been tightened too tight would mangle the nut and lead leakage Model Item Size of fitting pipe inch Max pipe length m Max height difference between indoor unit and outdoor unit m Amount of additional refrigerant to be filled for extra length of pipe Gas...

Page 29: ... be short and drooping gradient should at less 1 100 to prevent the formation of air bubble If drain hose cannot has enough drooping gradient drain raising pipe should be added To prevent bent of the drain hose the distance between hoisting stand should is 1 to 1 5m Use the drain hose and clamp attached Insert the drain hose to the drain vent and then tighten the clamp Entwine the big sponge on th...

Page 30: ...tion of the electric circuit Note Before obtaining access to terminals all supply circuits must be disconnected 118 b 15 Hose band Accessory a 300 Max c 50 Max 850 Max 1 25 to 1 100 down slope Drain hose Accessory Drain hose connection Hose band Accessory Drain hose Accessory Polyvinyl chloride VP25 Field supplied Total length of a b c shall be within 1100 mm 1 25 to 1 100 down slope Common drain ...

Page 31: ...troller 1 Wiring of the indoor unit Remove the control box lid pull the wires inside through rubber bush and wiring according to the WIRING DIAGRAM then tighten it with clamp 2 Wiring of the controller 1 Remove the control box lid pull wires inside through rubber bush and connect to the controller 2 Wrap the wire with sealing pad 3 After wiring tighten it with clamp and fix the control box lid Pre...

Page 32: ...ition by using the fixing screws M6 long screws 5 Attach the corner pocket after mounting air panel Refer to Fig 4 1 Catch the band at the rear side of the cover for corner pockets onto the projection of the panel 2 Catch the L shaped hook located at the rear side of the cover for the corner pockets onto the square hole of the air panel 6 Install corner pocket cover with display 1 cnnect lines of ...

Page 33: ...panel Connect the joints for swing louver motor lead wire installed on the panel Refer to Fig 7 Fig 5 Air leak Contaminator dew condensation dew dripping Air leak from ceiling No gap is allowed Adjustment of the indoor unit body from the holes in the corner of the panel is possible if the indoor unit is kept leveled and the dreinage pipe piping etc is unaffected Fig 6 Fig 7 motor wiring for auto l...

Page 34: ...e or exhaust remove it 3 Place of installation shall be strong enough to support the weight of outdoor unit and it shall be able to insulate noise and prevent vibration Ensure that the wind and noise from the unit will not affect your neighbors 4 Avoid direct sunshine over the unit It is better to set up a sun shield as the protection 5 Place of installation must be able to drain the rainwater and...

Page 35: ...essure of the vacuum watch remains 4 Take out the valve cover of the gas valve together with the liquid valve 5 Loosing the cord of liquid valve until the pressure rise to 0 bar 6 Dismantle the tube from the cover of the inlet for refrigerant then tighten the cover 7 Loose the valve cord of the gas valve as well as the liquid valve entirely 8 Tighten the valve cover of the gas valve and liquid val...

Page 36: ...ctive work is completed and the pipes are wrapped use seal material to block the hole in the wall so as to prevent rain and wind from entering the room G Position and Method of Installing Wire Controller The wire remote control must be installed by qualified installation technicians in accordance with installation drawing instruction the power should be shut of f before installation First select a...

Page 37: ...the terminal board of the air conditioning unit 3 User pliers to bend the end of the single wire so that a loop matching the screw size is formed 4 Put the screw through the loop of the single wire and fix the loop at the terminal board 2 Connection of multiple twisted wires 1 Use wire stripper to strip the insulation layer 10mm long from the end of the multiple twisted wires 2 Remove the screw at...

Page 38: ...t is better to use shielded cable or double twisted cable as the signal line of the wire controller Products Electric Installation Caution The unit should be reliably earthed if it is improperly earthed that may cause electric shock or fire Wiring layout Installation should be conducted by National Wiring Regulation The rated voltage and exclusive power supply must be adopted for the air condition...

Page 39: ...purposes It cannot be cut off and be fixed by screw otherwise it would cause electric shock The user must offer the reliable grounding terminal Please don t connect the grounding wire to the following places 1 Water pipe 2 Gas pipe 3 Blowing pipe 4 Other places that professional personnel consider them unreliable The power cable communication wire connection between indoor and outdoor Model Power ...

Page 40: ...ibrate or make noise Has gas leakage been checked May cause unsatisfactory cooling heating effect Is the thermal insulation of the unit sufficient May cause unsatisfactory cooling heating effect Is drainage smooth May cause condensation and dripping Is the main supply voltage the same as the rated voltage specified on the nameplate The unit may break down or components may burn out Are the lines a...