Notes for i
nstallation
Remove
Before removing air conditioner to the other place, you should
contact
the
seller firstly.
Then it must be done under the direction of the professional
technician. In addition, the charge of this must be paid.
Noise
Electric wiring
Install in a location where is firm enough to avoid the enlargement of noise
and vibration.
Don’t put anything in front of the outlet of outdoor unit to avoid increasing
noise.
Be sure that hot air o
r
noise will not inconvenience neighbors.
Please contact
the
seller as soon as there is strange noise during operation.
Please use the safety support.
Must connect with ground reliably.
The exclusive circuit must be used. But removable socket can’t be used because poor
contact of it can cause over heat or fire.
Don’t pull the power cord strongly.
In fixed circuit, there must be electricity leakage protection switch and leakage current
is less than 30mA.
Air switch (thermal-magnetic breaker) should be installed in the circuit and its capacityis
10A for 7K and 9K, 15A for 12K, 20A for 18K,
.
The fixed wiring should be more than
4.0
mm
2
in area.
Note:
Drain hose or tubing can be purchased locally to satisfy your particular needs.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring
Connecting method between air conditioners and power cord and interconnecting method
of each individual element with one another should accord with wiring diagram on the unit.
The air conditioner should be installed in accordance with national wiring regulation.
5