Page 38
1
J2
J1
Normally Open
Relay Contact
Audio Out
600 ohm
J3
f) Paging Interface (optional)
The WPS-2900 may be equipped with an optional module that allows the user to broadcast
siren tones, digital voice messages or public address through existing in-plant public address
systems.
The audio output of the Paging Interface Module is a 600 ohm, transformer coupled signal.
This output interfaces with most industry standard paging systems. A level adjustment
potentiometer allows the user to set the siren output to a desirable level, through the public
address system.
The Paging Interface Module also has an output relay that makes a 1 amp rated, contact
closure whenever the siren audio is active. This is typically used to perform the in-plant PA
microphone “Push-To-Talk” function.
Customer Interface
Connection
Output Function
J3-1
Audio Out
J3-2
Audio Out
J1-1
N.O., 1 Amp Contact
J1-2
N.O., 1 Amp Contact
Connector J2
(factory wired)
Input Function
1
Bias Input
2
PA Relay
3
Audio In
4
Audio In
5
+12VDC
6
Ground
7
not used
Fig. 20: Paging Interface Board