![Wheelock ZC-312 Installation Instructions Manual Download Page 17](http://html1.mh-extra.com/html/wheelock/zc-312/zc-312_installation-instructions-manual_968392017.webp)
1.
Set the "Zone Amplifier/Central Amplifier" select switches for each group as required. See switch symbol 1 . If a group is using a zone amplifier
or speaker amplifier, then that group's switch should be in the down position. If a group is using a central amplifier, then that group's switch should
be in the up position.
2.
Set the "Central Amplifier" select switch for each group, as required. See switch symbol 2 . If one central amplifier is used for both paging and
background music, then the switch should be in the down position. If two or more central amplifiers are used, one for paging and one or more for
background music, then the switch should be in the up position. If central amplifiers are not used, then the switch should be in the up position.
3.
Set the "One-Way/Talkback" select switches for each zone as required. See Switch symbol 3 . If a zone is to have talkback paging, then that
zone's switch should be in the up position. If a zone is to have one-way paging, then that zone's switch should be in the down position.
NOTE: All zones in groups using (selected for) zone amplifiers or speaker amplifiers are one-way paging zones. Hence, the individual zone
switches should be in the down position. Zones selected for talkback paging must be in groups selected for central amplifiers - See switch symbol
1 .
4.
Set the "Talk Battery" selector switch, symbol 4 :
A. To the "ON" position when connected to a telephone systems, unused CO line/trunk port, 600 ohm audio page port, or directly to a telephone.
B. To the "OFF" position when connected to a Wheelock TPI-100 Telephone Paging Interface for CO/Centrex line, or analog station level line
paging.
5.
Set the "TPI-100 Interface" selector jumper, symbol 5 :
A. To the "LO" position when connected to a Wheelock TPI-100 Telephone Paging Interface for CO/Centrex
line, or analog station level line paging.
B. To the "HI" position when the Wheelock TPI-100 Telephone Paging Interface is not used.
CAUTION:
These devices are not intended for use in hazardous locations as defined by the National Electrical Code (NEC) and by the National
Fire Protection Association (NFPA).
WARNING: CUSTOMER ASSUMES ALL RESPONSIBILITY FOR PROPER INSTALLATION OF INTEGRATED CIRCUIT CHIP(S) AND
ACKNOWLEDGES THAT THE UNIT SHOULD BE FULLY TESTED IN ACCORDANCE WITH THE PROCEDURE IN THE
ORIGINAL INSTALLATION MANUAL OR INSTRUCTIONS AS THOUGH THE FULL UNIT WERE NEWLY INSTALLED WITH THE
NEW INTEGRATED CIRCUIT CHIP(S) BEFORE BEING PLACED IN SERVICE. WHEELOCK INC. ASSUMES NO
RESPONSIBILITY IN CONNECTION WITH THE PROPER INSTALLATION OR TESTING OF THE NEW INTEGRATED CIRCUIT
CHIP(S).
IMPORTANT:
Read separate "ZC-312 chip replacement" installation instructions for information on the installation of new integrated circuit chip(s).
(see P82456 A)
P81982 K
Sheet 17 of 21