P83541 F
Sheet 4 of 6
+
_
+
_
+
_
+
_
+
_
+
_
+_
ZONE 1 OUT
ZONE 2 OUT
ZONE 3 OUT
ZONE 4 OUT
ALL CALL
POWER IN
AUDIO IN
Figure 5:
WIRING SPECIFICATIONS:
Cable
Size: 14-22
AWG
OPERATING INSTRUCTIONS:
When making a live emergency announcement from the SAFEPATH panel, use the Four Zone Splitter’s four zone ON/OFF switches
to select the zones to which the audio will be broadcast or use the panel’s ALL CALL switch to select all of the zones. To select a
zone, slide the zone ON/OFF switch up to the on position (Figure 6). The ZONE SELECT LED associated with the zone switch will
be lit if the zone is selected. The ZONE ALARM LED’s indicate to which zones audio is currently being broadcast.
The splitter will
allow zone selection of live announcements only.
Automatic or manual alarm operation will be through all zones.
The splitter detects audio wiring faults (opens and shorts) in the non-alarm mode only. During alarm paging the splitter allows the
selection of any or all zone outputs. The ALL CALL switch overrides all zone selections. To initiate ALL CALL, slide the ALL
CALL switch up to the on position. If there is a trouble in the output wiring or a trouble in the four zone splitter circuit, the trouble
condition will be reported to the respective amplifier card as a speaker wiring trouble and the SPK LED will be lit.
4-ZONE SPLITTER
SPL
ZONE SELECT LED'S
ZONE ALARM LED'S
ON
OFF
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ON
OFF
ON
OFF
ON
OFF
Figure 6: