Wheelock SPL Installation Instructions Manual Download Page 4

P83541 F 

Sheet 4 of 6 

 

+

_
+

_

+

_

+

_
+

_
+

_

+_

ZONE 1 OUT

ZONE 2 OUT

ZONE 3 OUT

ZONE 4 OUT

ALL CALL

POWER IN

AUDIO IN

 

Figure 5: 

 

WIRING SPECIFICATIONS: 

 
Cable 

Size:   14-22 

AWG 

 
 

OPERATING INSTRUCTIONS: 
 

When making a live emergency announcement from the SAFEPATH panel, use the Four Zone Splitter’s four zone ON/OFF switches 
to select the zones to which the audio will be broadcast or use the panel’s ALL CALL switch to select all of the zones.  To select a 
zone, slide the zone ON/OFF switch up to the on position (Figure 6).  The ZONE SELECT LED associated with the zone switch will 
be lit if the zone is selected.  The ZONE ALARM LED’s indicate to which zones audio is currently being broadcast.  

The splitter will 

allow zone selection of live announcements only.

  Automatic or manual alarm operation will be through all zones. 

 

The splitter detects audio wiring faults (opens and shorts) in the non-alarm mode only.  During alarm paging the splitter allows the 
selection of any or all zone outputs.  The ALL CALL switch overrides all zone selections.  To initiate ALL CALL, slide the ALL 
CALL switch up to the on position.  If there is a trouble in the output wiring or a trouble in the four zone splitter circuit, the trouble 
condition will be reported to the respective amplifier card as a speaker wiring trouble and the SPK LED will be lit. 

 
 

4-ZONE SPLITTER

SPL

ZONE SELECT LED'S

ZONE ALARM LED'S

ON

OFF

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ON

OFF

ON

OFF

ON

OFF

 

 

Figure 6: 

Summary of Contents for SPL

Page 1: ... the symbol All warnings are printed in bold capital letters SPECIFICATIONS Per UL 864 Table 1 SAA 40S 80S 80SE SALL 15S Audio Output Voltage 25 0V 70 7V 100 0V 0 5V Maximum Output Power Per Sub Zone 25 0W 70 0W 100 0W 30 Speaker Inputs Power Input Voltage 24VDC Audio Input Output Voltage 25 0VRMS 70 7VRMS 100 0VRMS or 0 5VRMS Input Current 40mA Standby with no zones selected 190mA with all zones ...

Page 2: ...P83541 F Sheet 2 of 6 4 MOUNTING HOLES FOR SPLITTER POWER SUPPLY PCB COVER Figure 1 4 ZONE SPLITTER 1 PCB STANDOFFS 4 POWER SUPPLY PCB COVER 1 Figure 2 ...

Page 3: ...ONE 1 Slide the zone disarrangement switch down to the 2 To override zone disarrangement slide the DISARRANGEMENT ACKNOWLEDGE DISARRANGEMENT DISARRANGEMENT DISARRANGEMENT ALL CALL press the push to talk switch on microphone deliver the message to all circuits DISARRANGEMENT position WARNING ZONE SELECT ALL CALL switch to ALL CALL MANUAL position NORMAL TROUBLE ZONE 4 ZONE 3 ZONE 2 ZONE 1 WARNING M...

Page 4: ...indicate to which zones audio is currently being broadcast The splitter will allow zone selection of live announcements only Automatic or manual alarm operation will be through all zones The splitter detects audio wiring faults opens and shorts in the non alarm mode only During alarm paging the splitter allows the selection of any or all zone outputs The ALL CALL switch overrides all zone selectio...

Page 5: ... for a specific installation must be obtained from the Fire Department d A priority voice message matrix must be submitted to the Fire Department for approval before the installation is performed and shall include the following information 1 The duration of each message 2 The content of each message 3 The duration of the audible and visual alarm signals prior to the initiation of the subsequent pr...

Page 6: ... SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIR...

Reviews: