background image

 

273 Branchport Avenue 
Long Branch, N.J.  07740 
(732)  222-6880 

INSTALLATION INSTRUCTIONS 

SERIES VL/VLP SIGNALS 

 

GENERAL: 

Wheelock's VL, VL1 and VLP Visible Signals are designed with dual lamps for extra visibility and dependability.  They are non-flashing incandescent 
lamp signals that can be used as a visible signal only or combined with an audible signal.  They can be used on a continuous or coded alarm system.  
 
The VLPS, VLPH and VLPM are flashing xenon strobe signals that are designed to be combined with an audible signal or speaker.  They are ideal for 
adding strobe capability to an existing audible signal installation and they offer maximum reliability and efficiency for effective visible signaling in fire and 
life safety applications.  They flash once per second on continuous (non-coded) alarm systems. 
 

SPECIFICATIONS: 

 

MODEL 

 

SIGNAL 

TYPE 

INPUT 

RANGE 

VOLTAGE 

INPUT 

CURREN

T(AMPS) 

CANDELA 

PER 

UL 1638 

 

MOUNTING 

OPTIONS 

VL-24 

Incandescent 

24VDC 

0.100 

  0.84cd 

VL1-24 

Incandescent 

24VDC 

0.100 

  0.84cd 

VLP-24 

Incandescent 

24VDC 

0.100 

  0.84cd 

C,D 

VLPS-24 

Strobe 

18-31VDC 

0.025 

    1.5cd 

C,D 

VLPH-24 

Strobe 

18-31VDC 

0.075 

  15.0cd 

C,D 

VLPH-115  Strobe  115VAC 0.060  

 

15.0cd  C,D 

VLPM-24 Strobe  24VDC 

0.088 

117.0cd E,F 

 

VLP, VLPS, VLPH & VLPM - POSSIBLE COMBINATIONS 

AUDIBLE SIGNAL 

OR SPEAKER 

WHEELOCK 

SERIES 

HORNS 

31T, 34T, EH-E 

BELLS (4", 6", 10") 

43T, 46T, 42PT, MB 

ELECTRONIC SIGNALS 

AES-E  * 

SPEAKERS 

ET-1010, 806T, 807T 

 

 

*  See Application Note 9. 

 
VL,VL1, VLP, VLPS, VLPH Models 
W in the model number indicates white lens; substitute R for red lens.  The VLPM is available with a clear lens.  NOTE: At 0 degrees C, minimum UL 
candela ratings apply:  15cd (70,000) models = 13.75cd 
 

WIRING DIAGRAM: 

                       

 

            Figure 1. 

 
VL and VL1 models have terminals with wire clamps, (2) wires - 12 AWG max. per position are allowed.  Do not pigtail or wrap wires around screw.  See 
Figure 1.  VLP, VLPS, VLPH and VLPM models have double leads for in-out wiring (See Application Note 2). 
 
Copyright 1986, 1989, 1990, 1991, 1992, 1993 Wheelock, Inc.  All rights reserved. 

P81415 N 

Sheet 1 of 4 