![Wheelock SAFEPATH SAPE-1AB Operation And Installation Manual Download Page 54](http://html1.mh-extra.com/html/wheelock/safepath-sape-1ab/safepath-sape-1ab_operation-and-installation-manual_968644054.webp)
SAFEPATH Manual
Sheet 55 of 78
Rev. C April 1999
Procedure I
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the AMP indicator on the SACM-4 module is on, an
amplifier trouble condition has occurred. An amplifier trouble condition may be caused by:
1.
Faulty internal wiring between the backplane module and the digital voice module.
2.
A faulty SACM-4 module.
3.
A faulty SADC module.
4.
A faulty backplane module.
Perform the following:
1.
Verify that the wiring between the backplane module and the digital voice module is intact.
2.
Replace the SACM-4 module.
3.
Replace the SADC module.
4.
Replace the backplane module.
Procedure J
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the AUDIO indicator on the SACM-4 module is on,
an audio output wiring trouble condition has occurred. An audio output wiring trouble condition may be caused by:
1.
Missing end-of-line resistor on the audio output.
2.
The audio output field wiring is open or shorted.
3.
A fuse on the SACM-4 module is blown.
4.
A faulty SACM-4 module.
5.
A faulty backplane module.
Perform the following:
1.
Verify that the end-of-line resistor is properly in place.
2.
Verify that the audio output field wiring is intact.
3.
Verify that all fuses on the SACM-4 module are intact.
4.
Replace the SACM-4 module.
5.
Replace the backplane.
Procedure K
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the STROBE indicator on the SACM-4 module is on,
a visual notification output wiring trouble condition has occurred. A visual notification output wiring trouble condition may be caused
by:
1.
Missing end-of-line resistor on the visual notification output.
2.
The visual notification output field wiring is open or shorted.
3.
A fuse on the SACM-4 module is blown.
4.
A faulty SACM-4 module.
5.
A faulty backplane module.
Perform the following:
1.
Verify that the end-of-line resistor is properly in place.
2.
Verify that the visual notification output field wiring is intact.
3.
Verify that all fuses on the SACM-4 module are intact.
4.
Replace the SACM-4 module.
5.
Replace the backplane module.
Procedure L
If the green NORMAL indicator is off, the yellow TROUBLE indicator is on, and the PWR indicator on the SACM-4 module is on, an
amplified speaker power output wiring trouble condition has occurred. An amplified speaker power output wiring trouble condition
may be caused by:
1.
Missing end-of-line resistor on the amplified speaker power output.
2.
The amplified speaker power output field wiring is open or shorted.
3.
A fuse on the SACM-4 module is blown.
4.
A faulty SACM-4 module.
5.
A faulty backplane module.
Perform the following:
1.
Verify that the end-of-line resistor is properly in place.
2.
Verify that the amplified speaker power output field wiring is intact.
3.
Verify that all fuses on the SACM-4 module are intact.
4.
Replace the SACM-4 module.
5.
Replace the backplane module.
Summary of Contents for SAFEPATH SAPE-1AB
Page 19: ...SAFEPATH Manual Sheet 20 of 78 Rev C April 1999 Figure 3 Operator s Console...
Page 24: ...SAFEPATH Manual Sheet 25 of 78 Rev C April 1999 Figure 5 DX 100 Module Illustration...
Page 25: ...SAFEPATH Manual Sheet 26 of 78 Rev C April 1999 Figure 6 DX 200 Module Illustration...
Page 28: ...SAFEPATH Manual Sheet 29 of 78 Rev C April 1999 Figure 7 SAFEPATH Panel Mounting...
Page 32: ...SAFEPATH Manual Sheet 33 of 78 Rev C April 1999 Figure 8 Typical System Block Diagram...
Page 62: ...SAFEPATH Manual Sheet 63 of 78 Rev C April 1999 Figure 30 Module Layout of the SAFEPATH Panel...
Page 63: ...SAFEPATH Manual Sheet 64 of 78 Rev C April 1999 Figure 31 SAFEPATH Panel Block Diagram...