Table 3B: Vertical Plane 

Vertical 15cd 

30cd 

75cd 

95cd 

Angle (in deg.) 

UL Min. 

Typ. 15cd 

UL Min. 

Typ. 30cd 

UL Min. 

Typ. 75cd 

UL Min. 

Typ. 95cd 

  0 

15.0 

20.5 

30.0 

43.3 75.0 102.6 95.0  146.0 

  5 

13.5 

20.5 

27.0 

43.3 67.5 102.6 85.5  146.0 

10 13.5 

18.3 

27.0 

38.4 

67.5 93.6 85.5  127.4 

15 13.5 

19.0 

27.0 

40.6 

67.5 97.4 85.5  131.9 

20 13.5 

18.7 

27.0 

40.9 

67.5 99.5 85.5  132.7 

25 13.5 

17.4 

27.0 

36.9 

67.5 88.5 85.5  121.9 

30 11.3 

16.6 

22.5 

34.3 

56.3 81.9 71.3  114.3 

35 11.3 

14.4 

22.5 

29.2 

56.3 70.2 71.3  101.5 

40 11.3 

13.4 

22.5 

26.9 

56.3 65.1 71.3  92.5 

45 11.3 

13.0 

22.5 

27.0 

56.3 66.5 71.3  93.1 

50 8.3 

10.8 

16.5 

21.6 

41.3 51.8 52.3  74.1 

55 6.8 

8.7 

13.5 

17.9 

33.8 43.0 42.8  60.2 

60 6.0 

8.0 

12.0 

16.5 

30.0 40.1 38.0  55.8 

65 5.3 

6.4 

10.5 

13.2 

26.3 31.5 33.3  44.8 

70 5.3 

6.3 

10.5 

13.0 

26.3 31.6 33.3  44.7 

75 4.5 

7.3 

9.0 

15.3 

22.5 36.9 28.5  51.9 

80 4.5 

5.4 

9.0 

11.0 

22.5 27.2 28.5  37.7 

85 3.8 

5.0 

7.5 

10.6 

18.8 25.8 23.8  36.0 

90 3.8 

4.8 

7.5 

9.5 

18.8 23.8 23.8  33.7 

 

 

SETTINGS: 

 

The switch on the PCB (SW1) is used to select the input voltage and sound output level, see Figure 1.  

 

                             Figure 1:                                                                           Figure 2: 
 

S W 1

1

2

3

4

SW1

1

2

3

4

ST+

ST-

+24

GND

AD+

AD-

TB1

ON

ON

 

POS 1 

POS 2 

POS 3 

POS 4 

SLIDE HERE FOR (0N)

SLIDE HERE FOR (OFF)

USE A SMALL SCREWDRIVER TO

CHANGE THE SWITCH POSITION.

 

 
 

Table 4:  Audio Input Voltage Mode Selection

 

Switch Settings (SW1) 

Audio Input Voltage Mode 

POS 1 

0.5 V RMS 

ON 

25 V RMS 

OFF 

 

Summary of Contents for SA-S90-24MCC-FR

Page 1: ...provide a synchronized strobe appliance when used in conjunction with a Sync Module SM Dual Sync Module DSM or Wheelock s Power Supplies listed for synchronization The Strobe uses a Xenon flashtube w...

Page 2: ...electable Appliance Input Impedance 0 5 V Setting Greater than 400 Ohms or equivalent to less than 1 1000 W 0 001 W or 1 mW load 25 V Setting Greater than 20 kOhms or equivalent to less than 1 32 W 0...

Page 3: ...output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies For exa...

Page 4: ...93 1 50 8 3 10 8 16 5 21 6 41 3 51 8 52 3 74 1 55 6 8 8 7 13 5 17 9 33 8 43 0 42 8 60 2 60 6 0 8 0 12 0 16 5 30 0 40 1 38 0 55 8 65 5 3 6 4 10 5 13 2 26 3 31 5 33 3 44 8 70 5 3 6 3 10 5 13 0 26 3 31...

Page 5: ...th respect to the reference level Sound Output Level 6 0 dB and are included only to assist the user in choosing a setting during installation However use the values in Table 1 not these values for th...

Page 6: ...vide sufficient wiring clearance for the installed product 7 Do not pass additional wires used for other than the signaling appliance through the backbox Such additional wires could result in insuffic...

Page 7: ...E NOT USED THEN A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW UNDER CERTAIN CIRCUMSTANCES MIGHT INDUCE A PHOTO SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY...

Page 8: ...ODUCT THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND EXPRESS IM...

Reviews: