![Wheelock SA-S90-24MCC-FR Installation Instructions Manual Download Page 2](http://html1.mh-extra.com/html/wheelock/sa-s90-24mcc-fr/sa-s90-24mcc-fr_installation-instructions-manual_968815002.webp)
P84503 C
Sheet 2 of 8
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY
BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE
THE APPLIED VOLTAGE TO THE STROBES.
SPECIFICATIONS (AMPLIFIER):
Table 1A: Sound Output Level
Sound
Level
Rated Reverberant dBA at
10 ft per UL 1480 for 0.5-V and 25-V Settings
6
84
5 81
4 77
3 74
2 71
1 68
NOTE:
See Table 5
Sound Output Level Selection
for use of settings “A” and “B”.
Power Input Voltage: 16.0 to 33.0 VDC, regulated
Current Consumption: 120 mA RMS maximum
Appliance Input Level: 0.5 V RMS or 25 V RMS (Switch selectable)
Appliance Input Impedance:
0.5-V Setting:
Greater than 400 Ohms, or equivalent to less than
1/1000 W (0.001 W or 1 mW) load
25-V Setting:
Greater than 20 kOhms, or equivalent to less than
1/32 W (0.03125 W or 31.25 mW) load
Sound pressure level measurements were made at 16 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with 25 V RMS
in the 25-V setting. Current measurements were made at 33 VDC with audio inputs of 0.5 V RMS in the 0.5-V setting and with
25 V RMS in the 25-V setting.
Reverberant dBA is a minimum UL rating based on sound measurements in a reverberant test room.
Table 1B: Strobe
Regulated Voltage
VDC/VRMS
Voltage Range
VDC/VRMS
Candela Mounting
Options
24 16.0-33.0
15/30/75/95
A,B
NOTES:
1.
The strobe will produce 1 flash per second over the "Regulated Voltage" range.