Wheelock RMS-2B Installation Instructions Download Page 4

P83270 B 

Sheet 4 of 5 

 
MEA INFORMATION: 
 
 

Recommendations - That the above units be accepted on condition that all uses, configurations, arrangements and functions, locations 
and installations comply with the New York City Building Code, specifically Subchapter 17 and with the Referenced Standard RS 17-
3 through 17-3C including the NFPA as appropriate, the UL Listing, the manufacturer’s instructions, the Fire Department Rules and 
the Electrical Code of the City of New York, and on further condition that: 
 
(a)  The use, installation and application of the SAFEPATH System shall be restricted exclusively to connection with an BSA/MEA 

approved compatible Class E, Class J or Class C Fire Command Station. 

 
(b)  The Fire Command Station shall have the capability of overriding any function of the SAFEPATH system. 
 
(c)  Prior to the installation of any SAFEPATH System, a specific approval for a specific installation must be obtained from the Fire 

Department. 

 
(d)  A priority voice message matrix must be submitted to the Fir Department for approval before the installation is performed and 

shall include the following information: 

 

1. 

The duration of each message. 

2. 

The content of each message. 

3.  The duration of the audible and visual alarm signals prior to the initiation of the subsequent prerecorded message 

transmission. 

4. 

The interval between the cessation of the audible and visual alarm signals and the generation of prerecorded message. 

 

(e)  The SAFEPATH panel must be located in the room as, and within 20 feet of a BSA/MEA approved Fire Command Station.  The 

wiring between the SAFEPATH Control Unit and the Fire Command Station must be enclosed in conduit. 

 
(f)  Power supply wiring to the SAFEPATH Control Unit shall be installed in the same conduit containing the input and output 

wiring. 

 
(g)  When used with central office communicator or transmitter, the installation and operation of the equipment and devices listed 

herein shall comply with Fire Department Rule #3 - RCNY 17-01, NFPA 71, and shall have the capability of transmitting 
separate and distinct signals to indicate manual pull station alarm, automatic smoke/heat detection alarm, sprinkler waterflow 
alarm, supervisory signal indications and trouble indications. 

 
(h)  The connection of security/burglar devices and equipment to that submitted for acceptance for fire alarm usage under this MEA 

application is prohibited within New York City and such equipment and devices shall be so permanently labeled. 

 
All shipments and deliveries of such equipment shall be provided with a metal tag suitably placed, certifying that the equipment 
shipped or delivered is equivalent to that tested and accepted for use, as provided for in Section 27-131 of the Building Code. 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Limited Warranty 

Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, 
maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more 
often and in accordance with local, state and federal codes, regulations and laws.  Specification, application, installation, operation, 