![Wheelock PRM-150 Installation Instructions Download Page 4](http://html1.mh-extra.com/html/wheelock/prm-150/prm-150_installation-instructions_968375004.webp)
P81537 G
Sheet 4 of 5
PRE-AMP
-2
4
V
T-
IN
R-
IN
GND
R-
OUT
T-
O
U
T
1 2 3 4 5 6
TO 24VDC
POWER SUPPLY
INPUT TO
AUDIO
SOURCE
OUTPUT TO
SPEAKER
AMPLIFIERS
Figure 7:
Simplified Schematic And Connection Diagram
OPERATION:
1.
Set PRM-150 volume control to position #5.
2.
Adjust each Speaker Amplifier's volume control to the desired volume level.
3.
If the desired volume level cannot be obtained at any or all speaker-amplifiers, then:
(A) Increase the PRM-150 volume control setting until the desired volume level is obtained at the speaker-amplifier(s) which
had the least volume.
(B) Readjust the other Speaker Amplifier volume controls, as required.
TROUBLE SHOOTING:
CONDITION CHECK
1. No audio output to Speaker Amplifiers.
1. Volume control turned up (clockwise).
2. Check presence and polarity of -24VDC and GND.
3. Check audio presence and level on T-OUT and R-OUT at PRM-150,
and if necessary also at the Speaker Amplifiers.
4. Check audio presence and level on T-IN and R-IN at PRM-150, and if
necessary at the audio source.
5. Defective unit - Replace.