Wheelock MT-241575W Installation Instructions Manual Download Page 5

P84155 M 

Sheet 5 of 6 

 

Figure C

8

8

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

 WOOD

#8-18 SCREWS

SCREW COVERS

 SCREWS

SURFACE MOUNTING

BACKBOX 

(IOB)

Figure D

8

8

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

#8-18 SCREWS

SCREW COVERS

CONCEALED CONDUIT MOUNTING

BACKBOX 

(IOB)

EXISTING

BOX IN WALL

 

Figure E

8

8

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

RETROFIT PLATE MOUNTING

SCREW COVERS

#8-32 SCREWS

BOX IN WALL

EXISTING FSB 

PLATE

RETROFIT

Figure F

8

8

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

SURFACE OR SEMI-FLUSH (4" X 2-1/8" BOX)

DBB OR 4" SQ. X 2-1/8"

DEEP BACKBOX

ISP EXTENDER

#8-32 SCREWS

SCREW COVERS

Figure G

8

4

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

SURFACE OR SEMI-FLUSH (4" X 1-1/2" BOX)

DBB OR 4" SQ. X 1-1/2"

DEEP BACKBOX

ISP EXTENDER

#8-32 SCREWS

SCREW COVERS

 

 

MOUNTING PROCEDURES: 

 

1.

 

The MT can be flush mounted to a 100mm backbox (Fig. A) or double-gang backbox (Fig. B).  It can also be surface mounted to a indoor/outdoor backbox (Figs. 
C & D).  It can also be used with a retrofit plate (Fig. E) or with an ISP extender (Figs. F & G).  Mounting hardware for each mounting option is supplied. 

2.

 

Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.  Do not pass additional wires (used for other 
than the signaling appliance) through the backbox.  Such additional wires could result in insufficient wiring space for the signaling appliance. 

3.

 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring space for the appliance. 

4.

 

Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  This is 
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

5.

 

Connect field wires to the MT  terminal block (polarity must be observed).  Bend the field wires up 90

°

 at the connection to the terminal block. 

6.

 

Carefully push the field wires into the backbox by hand.  Press the MT to the backbox, verifying that it is seated and aligned correctly. 

7.

 

Fasten the MT to the backbox using the screws supplied.   

 

WARNING:  THE MULTITONE STROBE APPLIANCE IS A “FIRE ALARM DEVICE – DO NOT PAINT”. 

WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING 

OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT 
CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE 
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION.  FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE 
AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

The MT-24MCW’s 110cd setting is Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority 
Having Jurisdiction. 

WARNING:  INSTALLATION OF WHEELOCK 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS SHOULD BE WALL MOUNTED AT 

LEAST 24" BELOW THE CEILING AS FOLLOWS:  (1) THE ON-AXIS (CENTER OF LENS) LIGHT OUTPUT SHOULD BE DIRECTED AT THE 
EYELIDS OF THE SLEEPING PERSON, E.G. PILLOW END OF BED, BED HEAD; (2) NO PART OF THE BED SHALL BE MORE THAN SIXTEEN 
(16) FEET FROM THE STROBE NOTIFICATION APPLIANCE.  INSTALLERS MUST ADVISE OWNERS AND OPERATORS OF BUILDINGS WITH 
SLEEPING OCCUPANTS, E.G. HOTELS AND MOTELS, TO WARN GUESTS, RESIDENTS AND EMPLOYEES TO NOT MOVE THE BED 
LOCATION TO A POSITION VIOLATING POINTS (1) AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY OCCUR DURING A 
FIRE EMERGENCY. 

WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER 

CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY.  STROBE REFLECTIONS IN A 
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE.  TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK 
STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW 
WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES.  WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE 
INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, 
STANDARDS, REGULATIONS, CODES AND GUIDELINES. 

Summary of Contents for MT-241575W

Page 1: ... SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS SPECIFICATIONS Table 1 UL ULC Listed Models and Ratings UL Ratings ULC Ratings Model Regulated Voltage VDC VRMS Voltage Range VDC VRMS Reverberant dBA At 10 Feet Voltage Range VDC VRMS Strobe Candela cd Anechoic dBA at 10 Feet MT 121575W 12 8 0 17 5 85 100 10 5 15 6 75 85 100 MT 24MCW 24 16 0 33 0 15 ...

Page 2: ...p STD 0 023 0 026 0 033 0 023 0 025 0 031 HI 0 032 0 036 0 045 0 074 0 082 0 103 Siren STD 0 021 0 023 0 029 0 018 0 020 0 025 HI 0 018 0 020 0 025 0 040 0 044 0 055 HI LO STD 0 013 0 014 0 018 0 011 0 012 0 015 WARNING CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT Table3 Current Ratings for 24MCW Models Strobe only Maximum RMS Current AMPS Voltage 15cd 30cd 75cd 110cd DC 16 33VDC...

Page 3: ...H MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING THE CANDELA SETTING THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION IMPROPER SETTING OF THE CANDELA SELECT SWITCH MAY RESULT IN OPERATION AT THE WRONG CANDELA WHICH COULD RESULT IN IN A CURRENT DRAW EXCEEDING THE POWER SUPPLY S CAPACITY Figure 2 Switch SW1 Settings POS 1 POS 2 POS 3 POS 4 SLIDE HERE FOR 1 SLIDE HERE FOR 0 USE A SMALL ...

Page 4: ...R END OF LINE RESISTOR TO NEXT STROBE OR EOLR FROM PRECEDING AUDIBLE OR FIRE ALARM CONTROL PANEL FACP FROM PRECEDING APPLIANCE OR FIRE ALARM CONTROL PANEL FACP EOLR Figure 5 Audible appliance and strobe operate in unison Red and black shunt wires are supplied GND FROM PRECEDING APPLIANCE OR FIRE ALARM CONTROL PANEL FACP STROBE AUDIBLE TO NEXT APPLIANCE OR END OF LINE RESISTOR EOLR BLACK RED MOUNTI...

Page 5: ...nto the backbox by hand Press the MT to the backbox verifying that it is seated and aligned correctly 7 Fasten the MT to the backbox using the screws supplied WARNING THE MULTITONE STROBE APPLIANCE IS A FIRE ALARM DEVICE DO NOT PAINT WARNING WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION...

Page 6: ...anada ULC National Electrical Code NEC Occupational Safety and Health Administration OSHA local state county province district federal and other applicable building and fire standards guidelines regulations laws and codes including but not limited to all appendices and amendments and the requirements of the local authority having jurisdiction AHJ Wheelock products when properly specified applied i...

Reviews: