Wheelock MT-241575W Installation Instructions Manual Download Page 4

P84155 M 

Sheet 4 of 6 

 

Table 6:  Switch Settings 

Tone 

POS 2 

POS 3 

POS 4 

Horn 1 

Bell 1 

March Time Horn 

Code 3 Horn 

Code 3 Tone 

Slow Whoop 

Siren 1 

HI/LO 0 

 

NOTE: 

 The Code 3 Horn and Code 3 Tone (set on HIGH dBA) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency evacuation 

signaling.  They should be used only for fire evacuation signaling and not for any other purpose. 

 

The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate independently.  All other 
tones are recommended for use only on continuous (non-coded)  

CAUTION:

  Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. 

 

WIRING DIAGRAMS: 

 

Figure 3: 

 

 

1.  Multitone Strobe models have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at 

each screw terminal.  Strip leads 3/8 inches and connect to screw terminals. 

2.  Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown in Figure 3.  The 

polarity shown in the wiring diagrams is for operation of the appliances.  The polarity is reversed by the FACP during 
supervision.

 

 

Figure 4:

 

Audible appliance and strobe operate independently.

 

-

+

AUDIBLE

STROBE

TO NEXT

AUDIBLE OR

END OF LINE RESISTOR

TO NEXT

STROBE OR

EOLR

FROM PRECEDING
AUDIBLE OR FIRE ALARM

CONTROL PANEL (FACP)

FROM PRECEDING

APPLIANCE OR FIRE ALARM

CONTROL PANEL (FACP)

+

-

+

-

+

-

+

-

+

-

(EOLR)

 

 

Figure 5: 

Audible appliance and strobe operate in unison.   

Red and black shunt-wires are supplied.

 

 

GND.

FROM PRECEDING

APPLIANCE OR

FIRE ALARM CONTROL

PANEL (FACP)

STROBE AUDIBLE

-

+

-

+

TO NEXT

APPLIANCE OR

END OF LINE

RESISTOR (EOLR)

BLACK

RED

(+) (-)

(+) (-)

 

 

MOUNTING OPTIONS: 

 

CAUTION:  

The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option.  If these 

limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. 

CAUTION:  

Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed 

multiconductor cable or 3/4" conduit fittings are used. 

 

Although the limits shown for each mounting option comply with the National Electrical Code, Wheelock recommends use of the largest backbox option shown and the 
use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring. 

Figure A

FLUSH (4" BOX)

#8-32 SCREWS

4" SQ. X 2-1/8"

DEEP BACKBOX

SCREW COVERS

8

4

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

Figure B

8

8

8

8

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

#6-32 SCREWS

SCREW COVERS

FLUSH (2-GANG BOX)

2-GANG x 3-1/2"
DEEP BACKBOX

 

Summary of Contents for MT-241575W

Page 1: ... SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS SPECIFICATIONS Table 1 UL ULC Listed Models and Ratings UL Ratings ULC Ratings Model Regulated Voltage VDC VRMS Voltage Range VDC VRMS Reverberant dBA At 10 Feet Voltage Range VDC VRMS Strobe Candela cd Anechoic dBA at 10 Feet MT 121575W 12 8 0 17 5 85 100 10 5 15 6 75 85 100 MT 24MCW 24 16 0 33 0 15 ...

Page 2: ...p STD 0 023 0 026 0 033 0 023 0 025 0 031 HI 0 032 0 036 0 045 0 074 0 082 0 103 Siren STD 0 021 0 023 0 029 0 018 0 020 0 025 HI 0 018 0 020 0 025 0 040 0 044 0 055 HI LO STD 0 013 0 014 0 018 0 011 0 012 0 015 WARNING CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT Table3 Current Ratings for 24MCW Models Strobe only Maximum RMS Current AMPS Voltage 15cd 30cd 75cd 110cd DC 16 33VDC...

Page 3: ...H MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING THE CANDELA SETTING THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION IMPROPER SETTING OF THE CANDELA SELECT SWITCH MAY RESULT IN OPERATION AT THE WRONG CANDELA WHICH COULD RESULT IN IN A CURRENT DRAW EXCEEDING THE POWER SUPPLY S CAPACITY Figure 2 Switch SW1 Settings POS 1 POS 2 POS 3 POS 4 SLIDE HERE FOR 1 SLIDE HERE FOR 0 USE A SMALL ...

Page 4: ...R END OF LINE RESISTOR TO NEXT STROBE OR EOLR FROM PRECEDING AUDIBLE OR FIRE ALARM CONTROL PANEL FACP FROM PRECEDING APPLIANCE OR FIRE ALARM CONTROL PANEL FACP EOLR Figure 5 Audible appliance and strobe operate in unison Red and black shunt wires are supplied GND FROM PRECEDING APPLIANCE OR FIRE ALARM CONTROL PANEL FACP STROBE AUDIBLE TO NEXT APPLIANCE OR END OF LINE RESISTOR EOLR BLACK RED MOUNTI...

Page 5: ...nto the backbox by hand Press the MT to the backbox verifying that it is seated and aligned correctly 7 Fasten the MT to the backbox using the screws supplied WARNING THE MULTITONE STROBE APPLIANCE IS A FIRE ALARM DEVICE DO NOT PAINT WARNING WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION...

Page 6: ...anada ULC National Electrical Code NEC Occupational Safety and Health Administration OSHA local state county province district federal and other applicable building and fire standards guidelines regulations laws and codes including but not limited to all appendices and amendments and the requirements of the local authority having jurisdiction AHJ Wheelock products when properly specified applied i...

Reviews: