background image

P84432 G 

Sheet 4 of 6

 

 

NOTE:  

The HS-24 must be set for Code 3 horn when used with the sync module.  Refer to Sync Module Installation 

Instruction sheets SM (P83123), DSM (P83177) and Wheelock’s Power Supplies for additional information.  If the HS-24 is 
connected to a coded system the continuous horn setting must be used 

 

 Figure 3:   

 

 

 
 
 

1.

 

HS-24 Appliance has in-out wiring terminals that accept two #12 to #18 American Wire Gauge 
(AWG) wires at each screw terminal.  Strip leads 3/8” inches for connection to screw terminals. 

2.

 

Break all in-out wire runs on supervised circuits or circuits in which supervision is used as shown 
in Figure 3.  The polarity shown in the wiring diagrams is for the operation of the appliances.  The 
polarity is reversed by the FACP during supervision. 

 
MOUNTING OPTIONS: 
 

CAUTION:  

The following figures show the maximum number of field wires (conductors) that can enter the backbox used 

with each mounting option.  If these limits are exceeded, there may be insufficient space in the backbox to accommodate the 
field wires and stresses from the wires could damage the product. 
 
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends 
use of the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional 
wiring room for easy installation and minimum stress on the product from wiring. 
 

4" SQ. X 2-1/8"

DEEP BACKBOX

FLUSH (4" BOX)

A

MAXIMUM NUMBER OF CONDUCTORS

AWG #18     AWG #16     AWG #14     AWG #12
      4                  4                    4                  4

#8-32 SCREWS

SCREW COVERS

FLUSH (2-GANG BOX)

B

2-GANG X 2-1/2"

DEEP BACKBOX

#6-32 SCREWS

SCREW COVERS

MAXIMUM NUMBER OF CONDUCTORS

AWG #18     AWG #16     AWG #14     AWG #12
      4                  4                    4                  4

  

SURFACE (INDOOR/OUTDOOR)

C

MAXIMUM NUMBER OF CONDUCTORS

AWG #18     AWG #16     AWG #14     AWG #12
      4                  4                    4                  4

IOB BACKBOX

WOOD

SCREWS

 #8-18 SCREWS

SCREW COVERS

CONCEALED CONDUIT MOUNTING

D

MAXIMUM NUMBER OF CONDUCTORS

AWG #18     AWG #16     AWG #14     AWG #12
      4                  4                    4                  4

SCREW COVERS

#8-18 SCREWS

IOB BACKBOX

EXISTING BOX

IN WALL

 