P84432 G
Sheet 2 of 6
Table 2: dBA Sound Output for 24VDC Models
Description
Volume
Reverberant Per UL 464
Anechoic dBA @ 10 Feet
16.0VD
C
24VDC 33.0VD
C
20.0VD
C
24VDC 31.0VDC
Low
80 83 86 86 90
92
Medium 85 88 91 91 95
98
Continuous
Horn
High
88 91 93 95 99 101
Low
75 79 82 86 90
92
Code 3 Horn
Medium
80
84
86
91
95
98
High
84 87 89 95 99 101
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY
BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO
DETERMINE THE APPPLIED VOLTAGE TO THE APPLIANCES.
Figure 1: ULC Directional Characteristics
81dB
83dB
-6dB
-3dB
95dB
-3dB
-6dB
85dB
-3dB
-3dB
-6dB
95dB
-6dB
20° 30°
80°
30°
27°
60°
48°
NOTES:
1.
The HS-24 is UL Listed for indoor use with a temperature range of +32
°
F to +120
°
F (0
°
C to +49
°
C) and maximum
humidity of 93%
±
2% RH.
WARNING: FOR UL APPLICATIONS THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE
LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). DO NOT
APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: FOR ULC APPLICATIONS THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE
LIMITS OF 20-31 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). APPLY
80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT AND TOTAL AVERAGE CURRENT
REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY
POWER SOURCES, SIGNALING CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK’S POWER
SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF
ANY FUSES ON THE CIRCUITS TO WHICH THIS APPLIANCE IS WIRED. OVERLOADING POWER SOURCES
OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT
OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.