Telephone Input Applications:
The AIM-3 can be connected to an unused CO Port, a page port, an analog station port ( with TPI-100 ) or to a zone control (MCZ-
144 ). When it is used for telephone paging, it should only be used for telephone paging only and not for background music. The
VOLUME adjust is used to set the telephone page volume. When using the AIM-3 with the single circuit SAFEPATH (SC-SAPE ),
verify the SC-SAPE controller software (U5) is Rev E or higher. When using the AIM-3 with other SAFEPATH panels, verify the
controller software (U3) is Rev D or higher. Failure to do so could result in improper operation.
AIM-3 SWITCH CONFIGURATION:
UNUSED CO PORTS
TIP
RING
UNUSED CO PORT
NC
NC
NC
NC
+
-
-
+
AUDIO
TXD
RXD/CC
POWER
CC
RMS-3 OF AIM-3
NC = NO CONNECTION
SWITCH
SEL. 1, SEL. 2
SEL. 3
PHONE
RM/PHONE
TALK BATT
POSITION
ON AS NEEDED
OFF
ON
PHONE
TALK BATT ON
Figure 4.
Unused CO Ports
AIM-3 SWITCH CONFIGURATION:
PAGE PORT
+
-
-
+
AUDIO
TXD
RXD/CC
POWER
CC
RMS-3 OF AIM-3
CONTACT
+
-
AUDIO OUT
CLOSURE
PAGE PORT
SWITCH
SEL. 1, SEL. 2
SEL. 3
PHONE
RM/PHONE
TALK BATT
POSITION
ON AS NEEDED
OFF
ON
PHONE
TALK BATT OFF