4.8. Accessory Output 2/Load Pump Control (BO-8)
Accessory Output 2 will be energized 60 seconds prior to the compressor output (BO-2) being energized. This
period is adjustable via the Medium User Interface and by the facility management system. When the compressor
output (BO-2) is turned off accessory output 2 will be continue to operate for a period that is also adjustable via
the Medium User Interface and by the facility management system. This output must be selectable for normally
open or normally closed operation by use of the facility management system, Service/Commissioning Tool, or
a user interface. The load water pump may be set to operate in either Sampled or Continuous mode. In the
Continuous mode, the load pump will run any time unit operation is enabled, both in Setpoint mode and S-Plan.
In the Sampled mode, the load pump will run during all compressor calls, and will cycle in a user-adjustable
fashion when no compressor calls exist, in order to allow a determination of the need to run the compressor. In a
domestic cycle, a pump sample period is _ of the domestic operation cycle length. In a comfort cycle, the sample
period is _ of the comfort operation cycle length. The sample length is 200 seconds initially, and is adjustable. In
the final 60 seconds of a sample operation, the temperature control logic is allowed to generate a compressor call
if indicated by the temperature/setpoint relationship. Sampling does not apply to Aqua-Stat mode of operation.
Welcome
EWT/Setpt
Oper Mode
XXX/XXX
Info Temp Stat Outputs Settings Maint History Alarms
WFI
E Series Reversible
Single Stage
Water-to-Water
Duplexed Load
Setpoint Controller
PROSSWWE-01
Info
Temperatures
Load EWT 57.2 ºF
Load LWT 49.0 ºF
Src EWT 59.6 ºF
Src LWT 66.0 ºF
Src Limit Temp 67.0 ºF
Load Limit Tmp 48.4 ºF
Src Limit 30.0 ºF
Load Limit 30.0 ºF
Temp
Status
Unit Status Auto
Y1/SysEna Off
O Status Htg
LoadFlow Off
Src Flow Off
Emg Shtdn Auto
BI-6
Off
PrimaryOvrd Off
HiPrsInp Off
LoPrsInput Off
Stat
Outputs
Comp Status Off
RevVlvStatus Htg
Alarm Status NML
LoadPmpStatus Off
SrcPmpStatus On
Settings
Dom Period 20Min
Comf Period 15Min
Dom Setpt 120.0 F
Htg Setpt 96.0 F
Clg Setpt 53.0 F
Unit of Measure F
Pump Oper. Sample
Sample Length 150 Sec
Y2 Clg Thrshld 2.0
Y2 Htg Thrshld 2.0
Y2 On Delay 120 Sec
Outputs
Settings
LOG_IN REQUIRED
User : <= maint =>
Code : 5667
Maint
Maintenance
Y1 Threshold 0.6
Y2 Threshold 2.0
Load OnDlyTime 5 min
CompStrtDly 90Sec
Hp Model HeatingOnly
SrcFlowSw Normal
LoadFlowSw Normal
Y2 Td Thrshld 2.0 F
Y1/Ena Auto
RevValve Auto
PrimaryOvrd Auto
ALARM SUMMARY
^/High Pressure
MUI for E Series Single Stage Water-to-Water
Alarms
Modes
Aquastat - Rev’ble
(Setpoint)
(S-Plan)
Reversible
(Htg Only)
(Auto)
Alarm #Events
Load Flow 0
Low Press 0
Src Freeze 0
Load Freeze 0
Src Flow 0
Hi Pressure 0
Loss Of Charge 0
SrcBadFrzSensor 0
Hi Temp Limit 6+
History
The parentheses are the
remaining possible values for
the non-parenthetical field.
The double-ended arrow
indicates a second page,
accessed by pressing the
right or left arrow button.
MUI for E Series Single Stage Water-to-Water