EKW FX10 INSTALLATION MANUAL
Electrical
Notes: All fuses are type “D” time delay (or HACR circuit breaker in USA).
Source pump amps shown are for up to 1/2 HP pump.
Load pump amps shown are for small circulators.
Unit
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Total Unit
FLA
Min Ckt
Amp
Max
Fuse
Max
Ckt Brk
RLA
LRA
EKW06
220-240/50/1
198/264
10.9
58.0
10.9
13.6
20
20
380-420/50/3
342/462
4.5
26.0
4.5
5.6
10
10
EKW08
220-240/50/1
198/264
15.4
82.0
15.4
19.3
30
30
380-420/50/3
342/462
5.1
35.0
5.1
6.4
10
10
EKW12
220-240/50/1
198/264
21.1
136.0
21.1
26.4
45
45
380-420/50/3
342/462
7.7
51.0
7.7
9.6
15
15
EKW17
220-240/50/1
216/264
25.0
149.0
25.0
31.3
50
50
380-420/50/3
342/462
10.6
75.0
10.6
13.3
20
20
All fuses type “D” time delay.