Relay 11/J73. Dead closing function (230V/400V 3-phase machine)
To use the closing function without a power supply, follow these instructions:
•
Contact the equipment to be controlled to contacts J73-103 and J73-104.
Relay 11/J73. 230V AC version (400V 3-phase machine)
To connect a 230V AC power supply to the contact, follow these instructions:
•
If a 230V AC version of J71 is fitted:
Connect J71-105 to J73-104 using a black 0.75mm² wire.
•
If J71 is not fitted or is not a 230V AC version:
Connect a black 0.75mm² wire from connector X10 to contact J73-104.
•
Connect the equipment to be controlled between contact J73-103 and
connector N1, N2 or N3 in the electrical cabinet.
Relay 11/J73. 230V AC version (230V 3-phase machine)
To connect a 230V AC power supply to the contact, follow these instructions:
•
If a 230V AC version of J71 is fitted:
Connect J71-105 to J73-104 using a black 0.75mm² wire.
•
If J71 is not fitted or is not a 230V AC version:
Connect a black 0.75mm² wire from connector X10 to contact J73-104.
•
Connect the equipment to be controlled between contact J73-103 and
connector X10 in the electrical cabinet.
Relay 11/J73. Relay 11. 24V AC version (230V/400V 3-phase machine)
To connect a 24V AC power supply to the contact, follow these instructions:
•
If a 24V AC version of J71 is fitted:
Connect J71-105 to J73-104 using a red 0.75mm² wire.
•
If J71 is not fitted or is not a 24V AC version:
Connect a red 0.75mm² wire from the 8-pin contact on the data card
labelled J69-8 to contact J73-104.
•
Connect the equipment to be controlled between contact J73-103 and
connector X10 in the electrical cabinet.