2.
Apply sealant/lubricant or Teflon tape to the male pipe threads. With any sealant
tape, the first one or two threads should be left uncovered to avoid system
contamination.
3.
Screw the connector into the port to the finger tight position.
4.
Wrench tighten the connector approximately 1 - 2 turns (to seal) from finger tight.
Again this is only reference - the fitting should
NOT
be over tightened.
2.2.2 Porting
Figure 4
2.2.3 Maintenance
Routine maintenance is usually confined to the periodic replenishment of Dow Corning
III lubricant or equivalent to spool and spring.