Table 4 Drive Fault Code (24K/36K)
Fault
code
Fault description
Possible reason
s
for
abnormality
How to deal with
1
Q axis current
detection,
failure in
drive control
1. C
ompressor wire
is not
connect
ed
properly
;
2.
Bad driver board components;
3.
Compressor start load is too large;
4.
Compressor demagnetization;
5. The c
ompressor
is short of oil, and
the
crankshaft
is worn seriously
;
6.
The compressor insulation
fails.
1.
Check
the
compressor wire;
2.
Change
the
driver board ;
3. Turn on the unit after the
pressure
is
balance
d
again;
4.
Change
the c
ompressor;
5.
Change the
c
ompressor;
6.
Change the
c
ompressor.
2
Phase current detection,
failure in drive control
1.
Compressor voltage default phase;
2.
Bad driver board components;
3.
The compressor insulation fault
.
1.
Check
the
compressor wire connection;
2.
Change the driver board;
3.
Change the Compressor.
3
Initialization, phase
current imbalance
Bad driver board components.
Change
the
driver board .
4
Speed estimation,
failure in drive control
1.
Bad driver board components;
2.
Compressor shaft
is
clamp
ed
;
3.
The compressor insulation fa
ils
.
1.
Change
the
driver board ;
2.
Change the Compressor ;
3.
Change the Compressor .
5
IPM FO output fault
1.
System overload or current
overload
s
.
2.
Driver board fa
ils
;
3. The compressor is short of oil, and
the crankshaft is worn seriously;
4.
The compressor insulation fault.
1.
Check the air
conditioner system;
2.
Change the driver board;
3.
Change the Compressor;
4.
Change the Compressor.
6
Communication
between driver board
and control board fault
1.
Communication wire connect
ion
is
not
well;
2.
Driver board fault;
3.
Control board fault
.
1.
Check
the
compressor wire connect.
2.
Change the driver board;
3.
Change the control board ;
7
AC voltage,overload
voltage
1.
Supply voltage input
is
too high or
too
low;
2.
Driver board fa
ils
;
1.
Check
the
power supply;
2.
Change the driver board;
8
DC voltage,overload
voltage
1.
Supply voltage input
is
too high ;
2.
Driver board fault;
1.
Check
the
power supply;
2.
Change the driver board;
9
AC voltage imbalance
Driver board fa
ils
;
Change the driver board;
10
The PFC current
detection circuit fault
before compressor is
ON
Bad driver board components
.
Change the driver board
.
11
AC voltage supply in
outrange
1.
Power supply
is
abnormal, power
frequency
is
out of range;
2.
Driver board
fa
ils
;
1. Check the system;
2. Change the driver board;
12
Products of
single-phase PFC
over-current, FO
output
at
low level
1.
System overload, current
is
too large;
2.
Driver board fault;
3.
PFC fault.
1. Check the system;
2. Change the driver board;
3. Change PFC.
Inverter over current
(3-phase power supply
air conditioners)
1.
System overload, current
is
too large;
2.
Driver board fault;
3. The compressor is short of oil, and
the crankshaft is worn seriously;
4.
The compressor insulation fault.
1. Check the system;
2. Change the driver board;
3. Change the Compressor;
4. Change the Compressor.
13
Inverter over current
1.
System overload, current
is
too large;
2.
Driver board fault;
3. The compressor is short of oil, and
the crankshaft is worn seriously;
4.
The compressor insulation fault.
1. Check the system;
2. Change the driver board;
3. Change the Compressor;
4. Change the Compressor.
14
PFC over
current(single
phase
air-conditioner)
1.
System overload, current
is
too large;
2.
Driver board fault;
3.
PFC fault.
1. Check the system;
2. Change the driver board;
3. Change PFC.
Phase imbalance or
phase lacks or the
instantaneous power
failure (only for
3-phase power supply
air conditioners)
1.3-Phase voltage imbalance;
2.
The 3-phase power supply phase
lost;
3.
Power supply wiring
is
wrong;
4.
Driver board fault.
1, Check the power supply;
2. Check the power supply;
3. Check the power supply wiring connect;
4.Change the driver board.
15
The instantaneous
power
off
detection
1.
The power supply is not stable ;
2.
The instantaneous power failure ;
3.
Driver board
fault
.
1. Check the power supply;
2. Not fault;
3. Change the driver board.
-
43
-
Summary of Contents for WHU09CTA21S
Page 55: ...Cassette grille Optional parts WH AG4CT1 1 2 3 4 5 54 Parts list ...
Page 57: ...Cassette grille Optional parts WH AG4CT2 1 2 3 4 5 6 7 8 9 56 ...
Page 63: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 62 Indoor unit WHU18CTA21S ...
Page 65: ... 64 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 Indoor unit WHU24CTA21S ...
Page 67: ...2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 66 Indoor unit WHU36CTA21S ...
Page 69: ...Outdoor unit WHU09SZA21S 68 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Page 70: ... Refrigerant cycle 69 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 ...
Page 71: ... Electrical parts 70 32 33 34 35 36 37 38 39 40 31 41 ...
Page 73: ...Outdoor unit WHU12SZA21S 72 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Page 74: ... Refrigerant cycle 73 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 ...
Page 75: ... Electrical parts 74 32 33 34 35 36 37 38 39 40 31 41 ...
Page 77: ...Outdoor unit WHU18SZA21S 76 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 ...
Page 78: ... Refrigerant cycle 77 17 18 19 20 21 22 23 24 25 26 27 28 29 30 35 31 34 48 32 33 ...
Page 79: ... Electrical parts 78 36 37 38 39 40 41 42 43 45 46 47 44 ...
Page 81: ...Outdoor unit WHU24SZA21S 80 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 ...
Page 82: ... Refrigerant cycle 22 23 24 25 26 27 28 29 30 32 33 34 35 36 31 81 37 ...
Page 83: ... Electrical parts 82 38 39 40 42 43 44 45 46 47 48 49 41 ...
Page 85: ...Outdoor unit WHU36SZA21S 84 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 ...
Page 86: ... Refrigerant cycle 85 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 33 31 ...
Page 87: ... Electrical parts 86 34 35 36 37 38 39 40 42 43 44 45 46 47 48 49 41 ...
Page 90: ......