Westinghouse Type F-122 Oil Circuit-Breakers
and the breaker to the panel.
The
breaker should be mounted as nearly
level as possible. The nipple supplied
with the breaker units should be screwed
into the rod end of the rear of the oper
ating handle and the mechanical set-up
will be complete.
By adjusting the
amount by which the nipple is screwed
into the rod end, it is possible to vary the
contacts in the breaker. This adjust
ment should be made in such a way that
full contact is obtained in the breaker
when the handle is latched closed. In
adjusting the breaker special care should
be taken to see that the toggle lever is
n
of an inch, or less, from the stop pin
in the closed position. See Fig. 3 and
instructions under "Adjustments."
If
this adjustment is not correct, the latch
load on the coverplate will be excessive
and the tripping attachments may not
function properly. With this adjustment
correct, the signal switch should make
good contact in both the open and closed
positions of the breaker. It should be
observed that proper contact in the
breaker is necessary in order to get
proper contact on the signal switch.
When the adjustment of the breaker
and signal switch is correct and oper
ating properly, then the tripping cores
can be put in place, and the nuts put on
which hold them. If an under-voltage
release is supplied, it may now be mount
ed on the coverplate and the leads thrust
through the clearance between the cover
plate and the panel, and then drawn
back through the holes drilled in the
panel for the leads.
For mounting other auxiliaries on the
switchboard mounting breaker, see des
cription under the heading of "Mounting
of the Auxiliaries". (See page 8).
Mounting of Remote Control
Breaker
The remote control breaker unit should
be mounted in place upon the wall or
pipe as nearly level as possible, and the
operating rod end reversed so that the
offset will be as shown in Figs. 3 and
9.
The auxiliary switch and bell alarm
contacts,
if
supplied, should be mounted
in the coverplate before the coverplate
is mounted on the panel or panel bracket.
The two extra bolts supplied with the
two-coil coverplate should be discarded.
The coverplate can then be mounted as
shown in Fig. 8, with the coils in place in
the coil
box.
The tripping cores can then
FIG. 6-SINGLE HANDLE 2-COIL COVERPLATE
be put in place on the coverplate and
tightened.
Here again, if an under
voltage release is used, it may be placed
on the coverplate after it is assembled
to the panel by pushing the leads through
the clearance between the coverplate
and the panel, and pulling them through
the drilled holes in the panel. All con
nections should be made after the me
chanical assembly is complete. The cover
plate and breaker units should then be
connected together with operating rods
through the bell cranks as shown in
Fig. 8.
The connecting pipes are %-inch
x strong pipe, and should be cut
4
inches
shorter than the distance between ful
crums of the levers to be connected.
These pipes should be threaded 2%
inches on each end with %-inch straight
pipe thread. A %-inch pipe lock nut
should be put at one end or the other
of each pipe, with the exception of the
breaker unit end. A pipe nut should
never be used on the breaker unit end.
The length of the pipe should be ad
justed so that the travel of each crank
lever is approximately equal on each
7
side of the horizontal or vertical center
line.
The last length should be ad
justed so that with the handle in the
latched position, the contacts in the
breaker are making full contact, as
previously described. With proper ad
justment on the breaker contacts, it
will be observed that proper contact is
secured on the signal switch if one is
used. The bell cranks as supplied are for
mounting above the floor. If it is de
sired to mount the bell cranks below the
floor, it is necessary to reverse them.
To reverse the bell cranks, remove the
fulcrum pin and replace it in the lower
hole. To reverse the accelerating device
it is necessary to remove the fulcrum
pin and to replace it in the upper hole.
It is also necessary to change the acceler
ating spring on the accelerating device.
See Fig.
7.
Any length of pipe exceeding
12
feet
should have an intermediate support. The
operating rods should all be in tension
except the one next to the breaker, and
in applications where this vertical rod
is long enough, to cause buckling under
www
. ElectricalPartManuals
. com