background image

Westinghouse  Type  F-122  Oil  Circuit-Breakers 

and  the  breaker  to  the  panel. 

The 

breaker  should  be  mounted  as  nearly 

level  as  possible.  The  nipple  supplied 
with the  breaker units should be screwed 
into  the  rod  end  of  the  rear  of  the  oper­

ating  handle  and  the  mechanical  set-up 
will  be  complete. 

By  adjusting  the 

amount  by  which  the  nipple  is  screwed 

into the rod  end,  it is possible to vary the 

contacts  in  the  breaker.  This  adjust­
ment  should  be  made  in such  a  way  that 
full  contact  is  obtained  in  the  breaker 

when  the  handle  is  latched  closed.  In 
adjusting  the breaker special care should 
be  taken  to  see  that  the  toggle  lever  is 

of  an inch,  or  less,  from  the  stop  pin 

in  the  closed  position.  See  Fig.  3  and 
instructions  under  "Adjustments." 

If 

this  adjustment  is  not  correct,  the  latch 
load  on  the  coverplate  will  be  excessive 

and  the  tripping  attachments  may  not 
function properly.  With this adjustment 

correct,  the  signal  switch  should  make 
good contact in both the open and closed 

positions  of  the  breaker.  It  should  be 
observed  that  proper  contact  in  the 
breaker  is  necessary  in  order  to  get 
proper  contact  on  the signal  switch. 

When  the  adjustment  of  the  breaker 

and  signal  switch  is  correct  and  oper­
ating  properly,  then  the  tripping  cores 
can  be  put  in  place,  and  the  nuts  put  on 
which  hold  them.  If  an  under-voltage 
release is supplied, it may now be mount­

ed on the coverplate and the leads thrust 

through the clearance between the cover­

plate  and  the  panel,  and  then  drawn 

back  through  the  holes  drilled  in  the 
panel for  the  leads. 

For  mounting  other  auxiliaries  on  the 

switchboard  mounting  breaker,  see  des­

cription under the heading of "Mounting 
of  the Auxiliaries".  (See  page  8). 

Mounting  of  Remote Control 

Breaker 

The remote control breaker unit should 

be  mounted  in  place  upon  the  wall  or 

pipe  as  nearly  level  as  possible,  and  the 

operating  rod  end  reversed  so  that  the 
offset  will  be  as  shown  in  Figs.  3  and 

9. 

The  auxiliary  switch  and  bell  alarm 
contacts, 

if 

supplied,  should  be  mounted 

in  the  coverplate  before  the  coverplate 
is mounted on the panel or panel bracket. 
The  two  extra  bolts  supplied  with  the 
two-coil  coverplate  should  be  discarded. 

The  coverplate  can  then  be  mounted  as 
shown in Fig.  8,  with the coils in  place in 
the coil 

box. 

The tripping cores can then 

FIG.  6-SINGLE  HANDLE  2-COIL  COVERPLATE 

be  put  in  place  on  the  coverplate  and 
tightened. 

Here  again,  if  an  under­

voltage  release  is  used,  it  may  be  placed 
on  the  coverplate  after  it  is  assembled 
to the panel by pushing the leads through 
the  clearance  between  the  coverplate 
and the panel,  and pulling  them through 
the  drilled  holes  in  the  panel.  All  con­

nections  should  be  made  after  the  me­
chanical assembly is complete. The cover­
plate  and  breaker  units  should  then  be 
connected  together  with  operating  rods 
through  the  bell  cranks  as  shown  in 
Fig.  8. 

The  connecting  pipes  are  %-inch 

x strong pipe,  and should  be cut 

inches 

shorter  than  the  distance  between  ful­
crums  of  the  levers  to  be  connected. 
These  pipes  should  be  threaded  2% 

inches on each end  with  %-inch  straight 
pipe  thread.  A  %-inch  pipe  lock  nut 
should  be  put  at  one  end  or  the  other 
of  each  pipe,  with  the  exception  of  the 

breaker  unit  end.  A  pipe  nut  should 

never  be  used  on  the  breaker  unit  end. 
The  length  of  the  pipe  should  be  ad­
justed  so  that  the  travel  of  each  crank 
lever  is  approximately  equal  on  each 

side  of  the  horizontal  or  vertical  center 

line. 

The  last  length  should  be  ad­

justed  so  that  with  the  handle  in  the 

latched  position,  the  contacts  in  the 

breaker  are  making  full  contact,  as 

previously  described.  With  proper  ad­

justment  on  the  breaker  contacts,  it 
will  be  observed  that  proper  contact  is 
secured  on  the  signal  switch  if  one  is 

used. The bell cranks  as  supplied  are for 

mounting  above  the  floor.  If  it  is  de­

sired  to  mount  the  bell cranks below the 

floor,  it  is  necessary  to  reverse  them. 

To  reverse  the  bell  cranks,  remove  the 

fulcrum  pin  and  replace  it  in  the  lower 

hole.  To reverse the accelerating  device 
it  is  necessary  to  remove  the  fulcrum 
pin  and  to  replace  it  in  the  upper  hole. 
It is also necessary to  change  the  acceler­
ating  spring  on  the  accelerating  device. 

See  Fig. 

7. 

Any  length  of  pipe  exceeding 

12 

feet 

should have an intermediate support. The 

operating  rods  should  all  be  in  tension 
except  the  one  next  to  the  breaker,  and 

in  applications  where  this  vertical  rod 
is  long  enough,  to  cause  buckling  under 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for F-122

Page 1: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 2: ... 8 Mechanical Interlock 8 Mechanical Sequence Interlock 10 16 Mounting of Auxiliaries 8 10 Overload Release 14 Panel Bracket 15 Panel Frame Mounting Bracket 15 Pipe Bracket 15 Pipe Structure 15 Signal Switch and Beii Alarm 10 Tripping Devices 10 Undervoltage Release Attachment 10 12 General Description 3 Installation 3 Insulating Oil o 6 Mounting of Circuit Breaker Units 0 6 Switchboard Breaker Pa...

Page 3: ...ection covering adjustment 5 Operate the circuit breaker by hand several times watching each pole and the operating mechanism to be sure all parts move smoothly and freely 6 When the mechanism is remote mounted adjust the connections between the breaker and operating mechanism so that full contact is obtained and the breaker rests on the bumpers when in the open position 7 Install connections to t...

Page 4: ... Toggl Lever Lmks Set toggle to this dim F Closing Lever Ooer RodEnd Assem foruu __ _ oush ordown 4 puff L_ Assem 11 for down pull operation Stationaryarc shield Tanh LiftRod t icarta il l 1 f t Terminal I I l Bushing Dash Pot IIIH Details FIG 3 BREAKER PoLE UNIT SIDE VIEW CRoss SEcTioN 4 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 5: ...increase as is the case with plain copper contacts carrying large currents In fitting new contacts it is unnecessary that perfect line contact be obtained With the comparatively soft material silver good contact is obtained after a few operations as the silver flows slightly under pressure If the silver contacts on the moving contacts are replaced use solder of at FIG 4 THREE POLE BREAKER UNIT FRO...

Page 6: ...s Only the highest grade such as Wemco C or other approved oil should be used in the breakers The oil should be new or at least thoroughly reconditioned by means of a filter press or centrifuge In any case before using it should be given a dielectric test which should show a minimum of 22 000 volts preferably 25 000 to 30 000 measured between l inch diameter discs spaced 1 inch apart Before fillin...

Page 7: ... two coil coverplate should be discarded The coverplate can then be mounted as shown in Fig 8 with the coils in place in the coil box The tripping cores can then FIG 6 SINGLE HANDLE 2 COIL COVERPLATE be put in place on the coverplate and tightened Here again if an under voltage release is used it may be placed on the coverplate after it is assembled to the panel by pushing the leads through the cl...

Page 8: ...k out device mounts on the side of the breaker unit and is attached to the breaker frame as shown in Fig 18 It is necessary to replace the standard pin in the breaker operating lever by the special large headed pin supplied with the device It should be observed that the armature moves freely and that with the armature closed the large headed pin has clearance to pass while wit hthe coil de energiz...

Page 9: ...2 Oil Circuit Breakers Arrangement for J pipe mtg hand oper mechanism 14 600 800Amps i I I Arrangement for lj wall mtg Mr l n I I FIG 8 REMOTE CoNTROL MouNTING DETAILS 9 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 10: ...lts clamps the undervoltage release tightly in the proper position After it is completely mounted operate it a few times by hand to see that the movement is free and that it operates properly See Fig 12 The automatic retrieve undervoltage release mounts on the right hand side of the coverplate in a similar manner It is necessary to bolt a reset pin to the trip lever of the coverplate to operate th...

Page 11: ...se Type F 122 Oil Circuit Breakers FIG DouBLE HANDLE 3 COIL COVERPLATE Stortinq ionrJ g FIG 11 DouBLE HANDL 2 CoiL CovitRPLATE FOR MoTOR STARTING EQuiPMENT 11 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 12: ...rang ents the two coil single handle coverplate is used on non automatic or automatic single throw breakers unless special requirements demand the three coil single handle coverplate The double handle coverplate is used with all automatic and non automatic motor starting combination of breakers A special assembly of this double handle coverplate can be used with motor starting combinations It is p...

Page 13: ...e careful to leave it bearing over its entire area The coils are marked with their style number the style number of the series resistor and the voltages and frequencies on which they may be used Reference to these should be made in all corre spondence regarding the device The device is made for use with or without resistor depending upon whether it is desired to trip the breaker by short circuitin...

Page 14: ...l dashpot is attached to the end of the moving core The calibration is then inscribed on the dashpot and is varied by screwing the pot into the cover The time is varied by changing the number of the holes in the bottom of the piston un covered by the cliaphragm Instanta neous tripping is possible because the check valve action of the washer at the time of tripping varies inversely with the amount ...

Page 15: ...n completely opened of angle iron provided with standard third if the running handle is not thrown pipe fittings and holes so that the breaker in within a very limited period of time unit is bolted to the angle iron and the after the starting handle is opened it angle iron is held to the pipe will be impossible to close the running Pipe Structure The pipe structure side without first throwing in t...

Page 16: ...draw it from in front of the running handle pin and allowing the running handle pin to raise as would occur if the running side of the circuit breaker had started to close Thus it is easy to see that it is impossible to close the running side of the circuit breaker until the starting side has been fully closed and has reached its full open 16 position At the opening of the circuit breaker the inte...

Page 17: ...IP COIL CO ECTIO S I I I OJ Di Bkr n co Orer ood Relay 8 lhpCoJ 01rect Tn 0 1 ii JAttachment G r Seriesljold mr Co FIG 26 B ScHE vtATic DIAGRAM oF CoNNECTIONS FOR DIRECT TRIP ATTACHMENT Mounting Surface C 0 0 II I I I 1 r I T 3 Q psol 440112201 110 I 0 I UV I UV II 241 Q l r II II II II 7 II I II 0 Transformer I 0 9 32 Dia 2 Mtg Holes For 1 4 Dia Fil Hd Mach Screws FIG 27 DRILLING PLAN AND OUTLINE...

Page 18: ...MEMORANDA w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Page 19: ... 3 CONN 119 Ann St HOUSTON 2 TEXAS 507 Dallas Ave HUNTINGTON I W VA 1029 Seventh Ave P O Box 1150 INDIANAPOLIS 2 IND 1560 Stadium Drive JACKSON MICH 120 W Michigan Ave JACKSONVILLE 6 FLA 1520 Prudential Bldg 841 Miami Road KANSAS CITY 6 MO 101 W Eleventh St LOS ANGELES 17 CALIF 600 St Paul Ave REV 7 56 LITTLE ROCK ARK 707 Boyle Bldg 103 W Capitol St LONG BEACH CALIF 2129 Pacific Ave LOS ANGELES 17...

Page 20: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Reviews: