Installation instructions
11
Do
not
operate
the
system
until
all
the
check points
have
been
cleared
.
(A) Ensure
that
the
stop
valves
of the
outdoor
unit
are
fully
opened.
(B) Ensure that the electric wires have been fully connected.
(C) Ensure that the electrical resistance is more than 2M
Ω
, by measuring
the
resistance
between ground
and the
terminal
of
the
electrical parts
.
If
not
,
do
not
operate
the
system until
the
electrical
leakage
is
found
and repaired
.
Test run function identification
Operate
the
thermostat to turn ON the equipment, then proceed test run.
Pay
attention
to
the
following
items
while the
system
is
running
.
Do not touch any of the parts by hand at the discharge gas side
.
Compressor chamber and pipes at the discharge
side will reach temperatures in excess of 194
℉(
90
℃).
T
est run should be performed after refrigerant piping, drain, wiring, etc. have been finished.
The air conditioner is provided with a crankcase heater. Ensure that the main power supply has been
turned ON for more than 6 hours ahead of power on preheating. Failure to do so may damage the
compressor.
●
Turn off the power
after test run is finished.
Installation of the equipment is complete after concluding the test run. For additional information, contact local
technical service center of our company for further information.
CAUTION
Test
run
Electrical Data
Max
.
Running
Current
(
A
):
REFER
TO
NAMEPLATE
Note
:
(1)
Follow local codes and regulations when field selecting wires. All the above are the minimum wire sizes.
(2) Transmission cable length is longer than 262ft. (80m), a larger wire size should be selected.
(3
) Install
main
switch
and
ELB
for
each
system
separately
.
Select
the
high
response
type
ELB
that is activated
within
0
.
1second
.
Recommended capacity to see outdoor equipment switch capacity.
1
.
When connecting the terminal block using stranded wire, make
sure to use the round crimp-style terminal for connection to the
power supply terminal block. Place the round crimp-style
terminals on the wires up to the covered part and secure in place.
2
.
When connecting the terminal block using a single core wire, be
sure to perform curing.
<Attentions
when
Connect the power supply wiring>
Terminal
Stranded wire
Single
core
wire
covered part
Round crimp
-
style terminal
Model
(Capacity)
Power Supply
ELB (Electrical Leakage Breaker)
Power Source
Cable Size
Transmitting
Cable Size
Rated Current
(A)
Nominal Sensitive
Current (mA)
24K
208/230V ~/60Hz
25
30
3×12AWG
5×16AWG
36K
208/230V ~/60Hz
35
30
3×10AWG
5×16AWG
48K/60K
208/230V ~/60Hz
50
30
3×8AWG
5×16AWG