28
13-TROUBLESHOOTING
Fault
Possible fault
Remedy
The fan does not
turn
There is no current
Check the circuit breaker / fuse
The thermostat is damaged
Check if there is power to the terminals of the fan (and/
or 0-10V signal for EC)
The cables are not
connected
Monitor the implementation of all electrical connections with
in the scheme
Capacitor broken
Replace the capacitor (AC motor)
Insufficient air flow
Dirty filter
Clean or replace the filter
Selected speed low
Select a higher speed (max or med)
Noisy fan
Damaged fan
Visually check that the fan is intact
Fan loose
Check that the fan is fixed firmly to the bottom of the box
Selected speed high
Select a lower speed (min or med)
In summer comes
out hot air or cold
air out in the winter
Water too hot
Check that the incoming water is less than 10 ° C
in summer or above 40 ° C in winter
Water flow low
Check that the dT between water input and
output is at most 7K
Valve closed
Check that all manual valves are open to interception
Pump route
The float has closed the valve for pump alarm
Valve Actuator broken
Check that the actuator has opened the valve
Air in the coil
Vent drums and pipes
Condensation on
the panel
Water too cold
Raise the water inlet temperature
Speed too low
Increase the speed of the fan (med or max)
Dripping from the
pan
Condensate drain clogged
Control the outflow of the exhaust pipe
Pan counter slope
Check that the tray is level or tilted slightly towards the drain
Float broken
The float switches the pump
Pump route
The pump does not work or is dirty (clogged)
Check v
alve stuck
The check valve prevents the passage of water
Water pipes are not
insulated
Insulate all chilled water pipes
Defective seals
Check seals of hole connection
Dirty pan
Clean the pan to allow the normal flow of condensate