8. CONFIGURATIONS 

 

8.1. Configuration: WRD + WBM 

8.1.1. Description 

This configuration is used in a plant where you want to monitor the energy flow of the

 battery 

(

Pic.

 A1). The WBM 

battery  monitor  must  be  connected  to  the  negative  battery  terminal  and  provides  for  the  calculation  of  the 
incoming and outgoing energy. (See dedicated product manual for more details). 
WRD allows configuring the WBM in the Setup menu 7.0 or 8.1: 

x

 

Select the correct profile according to the type of battery. 

x

 

Select the battery capacity (Ah) correctly, so that the WBM can correctly calculate the State of Charge (%) 
of the Battery. 

x

 

Set the thresholds for the two contacts controlled according to the State of Charge (%) of the Battery. 

The 'Discharge' contact can be exploited to control a device capable of disabling the load, thus determining the 
maximum discharge depth within which the battery will cycle. This contact also intervenes in case of protections: 
overcurrent, over temperature and under voltage. 
With the 'Charge' contact, normally, is controlled a device capable of disabling the charge as it intervenes in the 
event of protections: overcurrent, over temperature and overvoltage. 
Setting  the  thresholds  for  the  'Charge'  contact  it  can  also  be  controlled  according  to  the  SoC  in  case  some 
applications require it. 
 

8.1.2. Main screens 

In the following picture are described the graphic used in the various screens of the main menu. 
Take into account the notes shown in the pictures. 

 
 

8.2. Configuration: WRD + WRMxx

 (1 ..8) 

8.2.1. Description 

This  configuration  is  used  in  a  stand-alone  system  where  you  want  to  mainly  monitor  the  energy  production 
(

Pic.A2

). 

The  WRMxx  controllers,  which  can  be  paralleled  up  to  a  maximum  of  8,  are  used  to  charge  the  battery.  (see 
dedicated product manual for more details). 
The WRD allows to collectively  configuring  the most common parameters of all the WRMxx in the  Setup Menu 
7.0, while it performs this individually in the Setup Menu 8.2.: 

x

 

Select the correct profile according to the type of battery. 

x

 

Select appropriately the setting of the Load output 

x

 

Set the Low Battery threshold for the output Load. 

 
 - With the WRM30+: Load output can be exploited with setting 'SurPlus' to control or directly feed a load when 
the battery is charged and there is still energy from the PV modules so we have an excess of energy that in this 
way can be re-used. 
 

8.2.2. Main screens 

In the following picture are described the graphic used in the various screens of the main menu. 
Take into account the notes shown in the pictures. 

 

 

Summary of Contents for WRD

Page 1: ...WRD Remote display for WESTERN WRD SYSTEM Manuale utente User manual DĂŶƵĞů ĚĞ ů ƵƚŝůŝƐĂƚĞƵƌ Manual del usuario Benutzerhandbuch IT DE ES FR EN ...

Page 2: ...th the various compatible devices able to access all the parameters both for the display and for the management of the control functions The simple user interface with 128x64 display and 4 buttons allows an immediate visualization of all the parameters powers voltages charge and PV string currents energy meters data logger and events From WRD all Setup settings can be made for each single WRMxx co...

Page 3: ...FEATURES 6 5 MECHANICAL DIMENSIONS 6 6 FIXING OPTIONS 7 7 IOT PLATFORM FOR MONITORING AND REMOTE CONTROL 8 8 CONFIGURATIONS 9 8 1 Configuration WRD WBM 9 8 1 1 Description 9 8 1 2 Main screens 9 8 2 Configuration WRD WRMxx 1 8 9 8 2 1 Description 9 8 2 2 Main screens 9 8 3 Configuration WRD WBM WRMxx 1 8 10 8 3 1 Description 10 8 4 Configuration WRD Leonardo System 10 8 4 1 Main screens 10 9 MAIN ...

Page 4: ...net cloud is optional The WESTERN WRD SYSTEM must be configured by setting to each WRMxx controller a unique address from 1 to 32 while the WBM already has a fixed address 33 as in the case of connection with a Leonardo 34 2 1 Installation procedure 1 To install the WRD in a dry place there are two fixing options from the panel and with frame Pic 4 2 At the back you can access the electrical conne...

Page 5: ...sources The screens for each configuration are described below 2 3 System Setup In the menu 7 0 SYSTEM the system settings are executed the list of parameters changes according to the current configuration Detailed explanations are described in the chapter Configurations 2 4 Date Time Setup In the menu 7 1 DATE TIME you set the system clock and the time zone Timezone It is important to correctly s...

Page 6: ... 7 5 OTHERS screen press the UP botton so that appears and then press the OK button for 1 sec It is possible to enter the EDIT mode Pic 3 where it is allowed to modify the parameters by keeping pressed the EDIT button for 1 sec Entry into the EDIT mode is visible on the display by the presence of the cursors on the modifiable parameter For editing are used the INC DEC buttons press the SELECT butt...

Page 7: ...autodetect V Supply voltage range Vbatt 10 64 V Self consumption Pq 1 0 W Operating temperature Tamb 10 40 C Max cable section terminal Power and RS485 1 5 mm2 Weight 250 g Dimension LWH 160 x 95 x 27 mm Degree of protection IP20 Tab 1 Electrical features 5 MECHANICAL DIMENSIONS Pic 4 Mechanical dimensions ...

Page 8: ...WRD Manuale utente EN 7 6 FIXING OPTIONS Pic 5 Fixing options ...

Page 9: ... display time period x Reports of events related to the system such as alarms or useful information x Specific information of the system installed type capacity and battery voltage device firmware versions Pic 6 WEB Client Access to the portal The first time you log in to the WRM MONITOR interface you need to register Registration is carried out at the following link also valid for subsequent acce...

Page 10: ...d overvoltage Setting the thresholds for the Charge contact it can also be controlled according to the SoC in case some applications require it 8 1 2 Main screens In the following picture are described the graphic used in the various screens of the main menu Take into account the notes shown in the pictures 8 2 Configuration WRD WRMxx 1 8 8 2 1 Description This configuration is used in a stand alo...

Page 11: ...t can also be controlled according to the SoC in case some applications require it Considering that in CONTROLLER mode the charge made by the WRMxx is already controlled through the WBUS it is not necessary to exploit the Charge contact of the WBM The WRMxx controllers which can be paralleled up to a maximum of 8 are used to charge the battery See dedicated product manual for more details The WRD ...

Page 12: ...tatus bar System voltage Battery temperature Flash if out range System control in progress PAUSE pause charge Low voltage battery Battery voltage Flash if out range Phase of charge Bulk Abs Float End of charge voltage Battery voltage meter Status bar System voltage Battery temperature Flash if out range State of charge2 if not yet valid Flash if out range Battery power IN OUT Flash if out range Cu...

Page 13: ... Reset WBM counters2 n Menu Warning Date of Reset WRM counters1 Battery output counter from Reset MENU 4 0 PV A string PV B string n Menu Warning PV string voltage1 PV string current1 PV string power1 PV input displayed internal temperature PV input hardware Flash if over Temp MENU 3 0 Battery current IN OUT Flash if out range Photovoltaic variables Battery voltage Flash if out range Battery varia...

Page 14: ...10 2000Ah battery bank capacity to compute SoC 2 10 8 12 56V below this threshold the LOAD output is activated 1 24h 24h LOAD output always active 1 1 16h LOAD output active from sunset for the set hours 1 Only Night LOAD output active only during the night 1 Only Day LOAD output active only during the day 1 OnSurPlus LOAD output active only during an energy surplus 1 List displayed Settable value...

Page 15: ...If there is no card show NOT PRESENT and no information is available uSD CARD read the type of file system NONE FAT12 16 32 and calculates the free space on the card FIND WRD read and list the files one at a time by showing the name size and date of the last update At the end shows END LIST SAMPLE EVENT show the remaining time for the next sampling List displayed Settable value and descriptions Va...

Page 16: ...NS 008 1 secon DNS 255 2 secon DNS 255 3 secon DNS 255 4 secon DNS 255 OFF ON Disable Enable cloud connection to transfer data to the server 0 255 set the device IP Address 0 255 0 255 1 255 DHCP set the Network Setup automatically the other values will be ignored 0 255 set the subnet mask 0 255 0 255 0 255 0 255 set the Gateway IP Address 0 255 0 255 0 255 0 255 set the primary DNS IP Address 0 2...

Page 17: ... 0 0 WRMxx n 4 0 0 WRMxx n 5 0 0 WRMxx n 6 0 0 WRMxx n 7 0 0 WRMxx n 8 0 0 W INVERTER 0 0 U I Mode Basic OFF LINE ON LINE current status of cloud connection List Settable value and descriptions Value firmware revision of the WRMxx devices from 1 to 8 0 0 if device is not present current device IP Address current subnet mask current Gateway IP Address current primary DNS IP Address current secondar...

Page 18: ...nuale utente EN 17 Configuration with WRD WBM WRMxx 1 8 00 33 WBUS Address of the WBM device 0 32 WBUS Address of the WRMxx devices from 1 to 8 00 if device is not present 00 34 WBUS Address of the WI device ...

Page 19: ...FF disch 1 Ļ 25 ON disch 1 Ĺ 40 OFF charge 2 Ĺ 100 ON charge 2 Ļ 90 UPDATE FW 10 2000Ah battery bank capacity to compute SoC 2 List displayed Settable value and descriptions Value RUN CAUTION starts the procedure to update the firmware in the WBM device The firmware update file must be present in the uSD card 2 0 ON disch below this threshold the ALARM output 1 is activated Discharge OFF 2 OFF dis...

Page 20: ...5 12V 48 00 50 24V below this threshold the WRM30 goes into Low Battery status and deactivates the LOAD 1 24h 24h LOAD always active 1 1 16h LOAD active from sunset for the set hours 1 Only Night LOAD active only during the night 1 Only Day LOAD active only during the day 1 OnSurPlus LOAD active only during an energy surplus 1 1 8h time in Absorption phase before moving to Float phase 1 List displ...

Page 21: ...tem is set to the Genset value it defines the power necessary to charge the battery pack Defines the use of the MeterPort Port not used PV Pulse Used in case of system with AC configuration to connect the counter of photovoltaic production Genset By jumpering this port with the AUX1 input using the cable supplied it is possible to control the ignition of a generator when the battery percentage fal...

Page 22: ...F RESET RUN UPDATE FW RUN Tech Menu Psw 00 RUN Reset the WRD device List displayed Settable value and descriptions Value 0 FF password to access the Technical Menu CAUTION Technical Menu is reserved for factory checks RUN CAUTION starts the procedure to update the firmware in the WRD device The firmware update file must be present in the uSD card To start WKH SURFHGXUH SUHVV ERWK Ĺ DQG Ļ NH V auto...

Page 23: ... or other interventions different by the instructions supplied by us The warranty is not valid also in case of damages coming from transport and or incorrect storage of the product force majeure or catastrophic events frost fire floods lightning vandalism etc All of the above mentioned guarantees are the sole and exclusive agreement which supersedes any proposal or agreement oral or written and an...

Page 24: ...WRD Manuale utente A IT DE ES FR EN Appendice Appendix Annexe Apéndice Anhang ...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...ciété WESTERN CO Srl Tous droits réservés La reproduction et l utilisation des informations contenues dans le présent document sont interdites sans l autorisation écrite de WESTERN CO Srl Este documento es de propriedad de WESTERN CO Srl Todos los derechos reservados La reproducción y el utilizo de las informaciones contenidas en este documento son prohibidos sin el consenso de WESTERN CO Srl Dies...

Page 33: ......

Reviews: