Please check if

1. The inverter and mounting bracket have been correctly installed. 2. The inverter’s exposed metal surface has a

ground connection. 3. The resistance between

arrays and ground is greater than 1Mohm. 4. For any unused

PV

DC

terminals, there are

connectors inserted to the terminal and sealed with waterproof caps. 5. The grid voltage at the

DC

point of connection of the inverter is within the permitted range. 6. The

circuit breaker must be correctly rated and

AC

wired. 7. The cable communication connectors have been correctly wired and tightened.

Startup

Switch on the

switch after finishing the above checks, then switch on the

circuit breaker. When there is sufficient

DC

AC

power applied and the grid conditions are met, the inverter will start to operate automatically.

DC

Commissioning

4.

RS485/CT and

Connection

DRED

NOTICE

For

/

4777,

0 is supported.

AS NZS

DRM

Make sure the cover and the communication cable gland has been mounted properly and adequately

Step 1

Step 2

Wi-Fi/GPRS Connection

(Optional)

The stick is included in the scope of delivery as an option.

3.6.1 Tighten the stick into the COM1 port. Make sure the stick is

securely connected. Otherwise the communication cannot be built.

3.6.2 For the connection and configuration of the Wi-Fi stick please refer to

<HED-WF stick User manual> .

3.6

Step 3

Step 4

0.

....1.

75

0mm

2

Battery Wire Assembly and Connection

Meeting the following requirements is mandatory. All warranty rights will otherwise be invalid.

3.5.1 Make sure there is an external DC breaker (≥40A) connected for battery without buil -in DC breaker.

t

3.5.2 Please ensure the battery model is enlisted in the suggested list in the user manual. Provent reverse polarity connection!

3.5.3 If the Battery connectors are not assembled properly and locked into place, arc or overheat may be induced.

3.5

Step 1

Step 2

Step 3

Step 4

Step 5

Insert the stripped wire with twisted wires.

The wire ends have to be visible in the spring.

Make sure the spring is closed firmly.

REF GEN/0                 PIN2
COMLOAD/0             PIN3

CT+       PIN1

(White wire)

CT -        PIN4

(Black wire)

Open the spring using a blade screwdriver

Use a suitable and calibrated torque wrench,size
15.Use an open-jaw wrench,size 16, to hold the
connector in place.

2N·m

click

click

6mm

2

15mm

8mm

3.7

battery

CT

Adapter

the CT to an adapter if the wire is not long enough.

Connect
CT wire polarity (+/-) must align when connected.

87654321

PV Wire Assembly and Connection

Meeting the following requirements is mandatory. All warranty rights will otherwise be invalid.

3. .1 Maximum open voltage of each string is less than 600V.

4

3.4.2 Maximum short circuit current of each

input is less than inverter allowable limit.

PV

3.4.3 The string is well insulated to ground in all cases.

3.4.4 Make sure that the

connectors have the correct polarity.

DC

3.4.5 If the

connectors are not assembled properly and locked into place, arc or overheat may be induced.

PV

3.4

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

click

click

6

7mm

7mm

PV1-F/UL-ZKLA/USE2

PV1-F/UL-ZKLA/USE2

Assemble the connectors

2.6-2.9 N·m

Positive

Negative

Assemble the

cable ends

D4

Positive terminal

Negative terminal

Crimp pliers to cable ends

Note: Don't crimp this part!

Assemble the

cable ends

MC4

Positive terminal

Negative terminal

4-6mm

2

COM2

GUIDEWAY

2

3

1

4

Power+

-

Power
RS485A
RS485B

PIN1

2

PIN

3

PIN
PIN4

COM1

The download of the current warranty conditions is available on www.western.it
WESTERN CO. S.r.l. via Pasubio 1 / 3– 63074 San Benedetto del Tronto (AP) Italy
Tel. (+39) 0735 751248 Fax (+39) 0735 751254 VAT number: 01192450441
For more information, please download the user manual and other technical documents at www.western.it

DRED/CT

COM2

PER

RS485

COM1

PER

Summary of Contents for W-HHS-3000

Page 1: ...i vita dovuto alle alte tensioni nell inverter Prima di collegare qualsiasi cavo e componente elettrico assicurarsi che l interruttore CC e l interruttore CA siano spenti e non possano essere riattivati PERICOLO Inserire il conduttore in una ghiera adatta secondo DIN 46228 4 e crimpare Inserire i conduttori crimpati L N e PE nei terminali corrispondenti e serrare le viti coppia N m 2 3 Assemblare ...

Page 2: ...bbligatorio soddisfare i seguenti requisiti Tutti i diritti di garanzia saranno altrimenti invalidati 3 1 Assicurarsi che sia collegato un interruttore CC esterno 40A per la batteria senza interruttore CC incorporato 5 3 5 2 Assicurarsi che il modello della batteria sia incluso nella certificazione CEI 0 21 o nella lista di batterie compatibili In quanto è stato collaudato il collegamento di invers...

Page 3: ...nts please ensure the switch circuit breaker are switched DC AC and cannot be reactivated OFF DANGER Insert the conductor into a suitable ferrule acc to 46228 and crimp DIN 4 Insert the crimped conductors L N and PE into corresponding terminals and tighten the screws torque N m 2 3 Assemble the locking cap threaded sleeve and swivel nut together Screw the connector AC firmly into the socket Step 1 ...

Page 4: ...s are not assembled properly and locked into place arc or overheat may be induced 3 5 Step 1 Step 2 Step 3 Step 4 Step 5 Insert the stripped wire with twisted wires The wire ends have to be visible in the spring Make sure the spring is closed firmly REF GEN 0 PIN2 COMLOAD 0 PIN3 CT PIN1 White wire CT PIN4 Black wire Open the spring using a blade screwdriver Use a suitable and calibrated torque wre...

Reviews: