10. Output Characteristic Curves
The U/I output characteristic curve is optimized for the following applications:
-
When supplying loads with high switch-on currents, such as motors. The dynamic
boost of the power supply supplies up to 200% of the nominal power for 5 s. This
ensures that sufficient reserve energy is available; overdimensioning of the power
supply is not necessary.
-
For system extension. With the static boost, up to 125% of the nominal output power
is available for a sustained period (up to 40°C).
-
For fast energy storage charging (e.g., of batteries) to supply a wide range of loads.
The power supply operates in the nominal operating range. Energy supply
to the load is ensured.
Figure 15 U/I output characteristic curve