PS-60 User Guide 6125-2200
9. Device Connection Terminal Blocks
The AC input and
DC
output terminal blocks on the front of the power supply feature screw
connection technology.
For the necessary connection parameters for the connection terminal blocks, refer
to the technical data section
.
9.1 Input
The power supply is operated on single-phase AC systems or two outer conductors of three-
phase systems. The power supply is connected on the primary side via the INPUT L/N
connection terminal blocks
.
The power supply is approved for connection to TN, TT, and IT power grids with a
maximum phase-to-phase voltage of 240 V AC
.
Figure 12 Network configurations in star network
9.2 Protection of the Primary Side
Installation of the device must correspond to EN 61010 regulations. It must be possible to
switch off the device using a suitable disconnecting device outside the power supply. The
line protection on the primary side is suitable for this (see technical data section).
DANGER: Hazardous voltage
An all-pos. fuse must be present for operation on three-phase and DC systems.
Protection for AC supply