background image

__________________________________________________________________________________

   

 

 

 

 

 

 

 

3

 

 

 

  

 

 

 

thru  9.    The  TPA  fuses  are  numbered  1  thru  4 
for bus A and bus B.  
 

3.3.  Fuse  Alarm  circuitry  provides  1  set  of  form 
“C” contacts (C, NO and NC) for each bus (Bus A, 
and Bus B).  In the event of a fuse alarm or loss of 
input  power,  the  proper  relay  will  change  states, 
providing  a  connection  between  the  Normally 
Op

en  “NO”  and  Common  “C”

  terminals  for  that 

bus

.    The  normally  closed  “NC”  terminal  will 

open to high impedance.   

 
4.

  

INSTALLATION 

Please read completely before beginning. 
 
WARNING:

  

Installation should only be performed 

by an experienced Installer familiar with DC power 
distribution systems. 
 

This  product  must  be  installed  within  a 
RESTRICTED  ACCESS  LOCATION  where 
access is through the use of a tool, lock and 
key  or  other  means  of  security,  and  is 
controlled  by  the  authority  responsible  for 
the location.  This product must be installed 
and  maintained  by  TRAINED  SERVICE 
PERSONNEL ONLY. 

 

 

4.1. 

Unpack  and  inspect  the  Fuse  Panel  for 

possible  damage  incurred  during  shipping.    If 
damage is found, file a claim immediately with the 
carrier, and notify Customer Service. 

 

4.2. 

Once the panel is unpacked, verify that there 

are  three  mounting  brackets.    The  bracket  with  the 
vertical 

slot is used for both 1” and 1-1/4” hole spacing 

applications.    There  will  be  two  brackets  with 
horizontal  slots,  one 

will  fit  1”,  and  the  other  1-1/4”, 

hole 

spacing.  All three brackets are universal for 19” 

and  23”  rack  mount  spacing  (see  figure  4.2.1)  and 
can  be  mounted  so  the  panel  can  be  installed  for  a 
flush  mounting  or  5”  offset.    Adjust  the  position  and 
orientation  of  the  correct  mounting  brackets  on  the 
fuse  panel,  such  that  it  will  fit  the  rack  you  wish  to 
mount the panel in.  Please see drawing 1123-19 on 
page 6 for mounting bracket configurations.

  

 

4.3. 

Mount  the  panel  on  the  equipment  rack 

using  the  thread  forming  #12-24  rack  mounting 
screws and tooth lock washers provided. 

Rack Mount Instructions: 

Elevated  Operating  Ambient

  -  For  closed  or 

multi-unit  rack  assemblies,  the  operating  ambient 
may be greater than room ambient.  Take care to 
install 

the 

equipment 

in 

an 

environment 

compatible 

with 

the 

maximum 

ambient 

temperature (Tma) specified by the manufacturer. 
 

Reduced  air  flow

  -  Installation  of  the  equipment 

in  a  rack  should  be  such  that  the  amount  of  air 
flow 

required 

for 

safe 

operation 

is 

not 

compromised. 
 

Mechanical Loading

 - Mounting of the equipment 

in  the  rack  should  be  such  that  a  hazardous 
condition  is  not  achieved  due  to  uneven 
mechanical loading. 
 

Circuit  Overloading

  -  Consideration  should  be 

given  to  the  connection  of  the  equipment  to  the 
supply circuit and the effect that overloading of the 
circuits  might  have  on  overcurrent  protection  and 
supply  wiring.    Appropriate  consideration  of 
equipment  nameplate  ratings  should  be  used 
when addressing this concern. 
 

Reliable  earthing

  -  Reliable  earthing  of  rack-

mounted  equipment  should  be  maintained.  
Particular  attention  should  be  given  to  supply 
connections  other  than  direct  connections  to  the 
branch circuit. 

 

19 " MOUNTING

23" MOUNTING

 

 

Figure 4.2.1

 

 

 

 

WARNING:

  For  safety  reasons  all  wiring  should 

be  done  with  all  power  sources  removed  (when 
possible).  

 

Note:

 A readily accessible disconnect device shall 

be incorporated in the building installation wiring. 

Summary of Contents for NPTPA1123

Page 1: ...ses per panel 120 Amps bus maximum 5 GMT style fuses per bus 20 Amp GMT fuse max 50 Amps per GMT bus max 4 TPA style fuses per bus 50 Amp TPA fuse max 120 Amps per TPA bus max Normal and Alarm LEDs fo...

Page 2: ...if you do not wish to extend the alarms you don t have to do anything with the alarm pins The Normal condition of the relay exists when the panel is powered up without any blown fuses The local alarm...

Page 3: ...nstalled for a flush mounting or 5 offset Adjust the position and orientation of the correct mounting brackets on the fuse panel such that it will fit the rack you wish to mount the panel in Please se...

Page 4: ...ed to the rack ground From step 4 3 the panel should already be ground to the rack via the 12 24 thread forming rack screws and outside tooth lock washers In addition to grounding via the mounting bra...

Page 5: ...12 A Yellow Green 15 A Red Blue 20 A Green White Table 4 12 1 Chassis Grounding Depending on the bus input current being supplied the chassis bonding conductor used should meet the minimum requirement...

Page 6: ...Current Display 0 to 199 ADC 1 A resolution 3 We recommend that you size fuses such that they do not run at more than 70 of their rating Thus a 20A fuse should not be run at more than 14 A TPA fuses...

Page 7: ...pment by anyone other than an authorized Westell representative will void the warranty 7 2 Westell will repair or replace any defective Westell equipment without cost during the warranty period if the...

Page 8: ...__________________________________________________________________________________ 8 Noran Tel Mounting Options...

Page 9: ...______________ 9 Noran Tel 1 2 3 4 C NC NO BUS A C NC NO BUS B ALARMS 9 8 7 6 5 9 8 7 6 5 1 2 3 4 A BAT RTN TPA TPA BAT A RTN GMT 9 8 7 6 5 GMT 9 8 7 6 5 BAT B RTN B BAT RTN TORQUE 1 4 STUDS TO 5 5 FT...

Page 10: ...__________________________________________________________________________________ 10...

Reviews: