background image

Section BXM‐301‐10H‐20A

030‐101901 Rev. A

R

14

1608IARA

Figure 19. Clean the Air Intake/Exhaust Holes

remove any debris

from the vent holes

Periodically 

Top and bottom mounting

brackets not shown

ÖÖ

ÖÖ

ÖÖ

3.17

Performing Cabinet Housekeeping

Verify all equipment is secure, verify all wires and cables are
neatly organized and managed, verify all bonding and ground­
ing connections are made at the ground plate, and verify no
equipment, tie‐downs, cables, or wires will interfere with the
closing of the door. Clean up the installation site per company
practice.

3.18

Closing and Locking the Cabinet

Upon completion, the installer should close and lock the cabi­
net by tightening the door's cup‐washer screw. The customer
may optionally lock the door with a padlock (customer sup­
plied) through the holes provided for it at the bottom of the
door‐lock flanges.

4.

MAINTENANCE

The Westell

r

 Boxer

t

 components are maintenance‐free,

however, please note the following item.

S

At least once every six months, inspect the Boxer‐30 cabi­
net to remove any debris from the fan cover's screened
holes (Figure 19). This facilitates proper operation of the
cabinet and allows unobstructed air flow.

5.

SERVICE AND REPAIRS

Replacing parts is the only recommended type of field repair
for the Westell

r

 Boxer

t

 cabinet. The list below contains the

only Boxer parts which may be ordered and field‐replaced (see
Part 6 for a telephone number, Table 2 for part numbers, and
Paragraph 7.2 for the return procedure).

Field‐replaceable parts:

S

Heat exchanger

‐ CAUTION ‐

To avoid electrical shock, turn off any power feeds to the
equipment being replaced or serviced, before removing or
replacing the equipment.

5.1

Replacing the Heat Exchanger

The Heat Exchanger cannot be field 

repaired

. Should a prob­

lem be suspected with the heat exchanger, it must be replaced.
Follow the steps below and see Figure 20 to replace the heat ex­
changer. Refer to Table 2 for the replacement heat exchanger
part number.

ÖÖ

ÖÖ

ÖÖ

ÖÖ

ÖÖ

Figure 20. Field Replacement of Heat Exchanger

Location of

top two nuts

Location of

four lower bolts

Heat exchanger

Hole for AC

power cord

(1/4‐20)

(1/4‐20)

Top and bottom mounting

brackets not shown

Ö

Ö

Ö

‐ CAUTION ‐

Westell recommends that two people be used to replace the
heat exchanger, one to hold the exchanger box on the outside
of the door, and one to remove/attach hardware on the inside
of the door.

1.

Open door, unplug power cord. 

Open the Boxer‐30 door,

and unplug the heat exchanger's power cord from the AC
outlet box inside the Boxer‐30.

2.

Detach and set aside the four bottom bolts. 

On the inside

of the door are 4 bolts that secure the bottom part of the
heat exchanger box to the door. Remove the four bottom
bolts, see Figure 20 for the location of the bolts.

3.

Detach and set aside the two top nuts

. On the inside of the

door are 2 nuts that secure the top part of the heat ex­
changer to the door. While another person on the exterior
side of the door holds the exchanger box, remove the two
top nuts. Keep the nuts for the new unit.

4.

Lift exchanger box off the door. 

From the exterior side of

the door, lift and pull off the heat exchanger box from the
door, allowing the two top bolts to exit out the top holes
and feeding the power cord out the hole provided for it at
the top right inside corner of the door. Set aside the unit
being replaced.

5.

Open and inspect the replacement unit. 

Open the shipping

box for the new heat exchanger, examine the unit for any
shipping damages. If no damage is present, the new unit
may be mounted.

6.

Lift new unit and feed power cord through the hole. 

With

one person on each side of the opened door, lift the heat
exchanger. Feed the AC power cord through the hole
provided for it at the top right 

inside

 corner of the door.

7.

Hang unit from top two holes. 

Align the two protruding

bolts on the back side of the exchanger with the two top
holes on the door which were vacated by removing the old
exchanger. Verify the AC cord is hanging freely on the in­
side of the door. Insert the two top bolts through the top

Summary of Contents for A90-BXM3019-10HE

Page 1: ...3 Product Purpose and Description Boxer 30 is an actively cooled NEMA 4 outdoor cabinet that can house and protect a wide range of electronic equipment Up to 30 vertical RUs 52 5 of 19 inch wide inter...

Page 2: ...t shown ware must be capable of supporting the weight of the Boxer 30 cabinet plus the weight of any equipment mounted in it The Boxer 30 cabinet is typically located at the customer premises but can...

Page 3: ...nting brackets at the top and bottom of the cabinet facilitate wall and H frame mount ing The bottom floor of the main cabinet contains numerous differently sized intact knock outs Paragraph 2 1 2 6 t...

Page 4: ...kets one at the top and one at the bottom of the cabinet come factory installed Figure 7 Mounting Brackets for Wall H Frame Mounting Top Exterior Mounting Bracket note the keyholes Bottom Exterior Mou...

Page 5: ...moved forward 2 or backward 3 if a few additional inches of equipment depth is needed at either the front or back of the channel Seven slots are provided for seven channel positions see Figure 2 Each...

Page 6: ...internal temperature reaches 70_F 21 1_C and will reach full speed when the internal tem perature reaches 80_F 26 7_C The external heat exchanger fan will turn on at 10 speed when the external temper...

Page 7: ...ro vided E This product should be operated only from the type of power source indicated on the marking label F Never push objects of any kind into this product through cabi net slots as they may touch...

Page 8: ...ut type and regardless of the order of the mounting steps All knock outs should be knocked out from the inside of the cabinet except for the small 0 575 knock outs which are to be knocked out from the...

Page 9: ...ttom mounting bracket and H frame rail Verify the cabinet is in the proper horizontal position make any needed ad justments then securely tighten all mounting hardware 6 Test installation firmness Tes...

Page 10: ...cabinet then marking the mounting hole loca tions or by measuring without lifting the equipment as a template Two of the mounting bracket holes are 16 apart on centers to facilitate mounting on standa...

Page 11: ...met or liquid tight fitting Install ei ther conduit and an appropriate and liquid tight fitting or a rubber grommet in the knock out hole 4 Route ground wire through knock out hole Run the ap proved g...

Page 12: ...applied in Para graph 3 12 3 Verify the knock outs are removed Perform the steps in Paragraph 3 5 to remove any appropriate cabinet hole knock out s and to install an appropriate fitting or grom met...

Page 13: ...laced inside the cabinet does not exceed the maximum weight requirement for the mounting structure surface and type 4 Determine the best mounting location for each piece of equipment for maximum capac...

Page 14: ...ble 2 for the replacement heat exchanger part number Figure 20 Field Replacement of Heat Exchanger Location of top two nuts Location of four lower bolts Heat exchanger Hole for AC power cord 1 4 20 1...

Page 15: ...er from Westell Once an RMA number is obtained return the defec tive unit freight prepaid and a brief problem description to Voice 630 375 4457 email rgmdept westell com Replacements will be shipped i...

Page 16: ...ncy Specifications The Boxer 30 cabinet is designed to meet the following regula tory safety or environmental specifications or requirements S NEMA 4 compliant 9 APPENDIX A PRODUCT VIEWS Figure 21 Bot...

Page 17: ...Section BXM 301 10H 20A 030 101901 Rev A R 17 1608IARA Figure 22 Front Exterior View of Boxer 30 Cabinet 35 4 60 6 24 4 24 0 56 8 17 8 2 0 18 4 Top and bottom mounting brackets not shown...

Page 18: ...Section BXM 301 10H 20A 030 101901 Rev A R 18 1608IARA 18 3 21 3 29 6 60 6 56 8 Figure 23 Exterior Right Side View of Boxer 30 Cabinet Top and bottom mounting brackets not shown...

Reviews: