background image

Section 311-610-20B

030-101522 Rev. C

21

0509IBRC

be put in loopback. The TL1 instruction sequence is outlined in
Appendix C of this document.

9.3.1

Remote Provisioning via 16-Bit Commands

To initiate a remote provisioning session, the NIU is first put into
loopback. While in loopback, the test person sends the appropri-
ate provisioning code to the NIU. Each code consists of a 16-bit
pattern and can be unframed, SF or ESF framed. All codes must
be sent to the unit for minimum of five seconds. In order to see
a bit-error response from the unit, the code must be present for
a minimum of 20 seconds. The unit will respond to the code with
bit errors after the 20-second time frame. Provisioning codes
and responses shown in Appendix A.

9.3.2

Remote Query of Provisioned Parameters via 16-Bit
Commands

The NIU also allows the test person to query the NIU and deter-
mine its provisioned options. To initiate a remote query session,
the NIU is first put into loopback. Once in loopback, the test per-
son sends the appropriate 16-bit query code to the NIU. All
query codes must be sent to the unit for minimum of five sec-
onds. In order to see a bit-error response from the unit, the
query code must be present for a minimum of 20 seconds. Query
codes and responses are shown in Appendix B.

9.4

Power

9.4.1

Local Power Input Lead Fusing

The NIU offers a flexible powering option which will allow the
unit to operate directly from T1 metallic spans, or from a locally-
provided 22 to 56Vdc source. The NIU is fused on its local power
input lead, pin 35, to prevent the failure of an individual NIU
from affecting other units on the same local power supply. This
fuse is not field replaceable since failure is an indication of an in-
ternal fault of the unit.

- NOTE -

The 3116-10 is equipped with an on-board 3V Lithium battery. If power
is removed from the circuit for whatever reason, the battery circuit is en-
abled to maintain the real-time clock circuit. If the battery ever needs re-
placement, the unit must be returned to Westell.

9.4.2

PCB Powering Option Switch

The unit contains an option to configure the unit for either span
or local powering. The option must be set at the time of installa-
tion. Figure 12 shows the location of this option. Select either
SPAN or LOCAL, as required by the application.

10.

TESTING & TROUBLESHOOTING

10.1

Testing and Field Repairs

This equipment should not be field repaired. If the equipment
is suspected of being faulty, replace it with another unit, op-
tioned identically, and retest. If the replacement unit appears to
operate correctly, the original unit may be faulty and should be
returned to Westell for repair or replacement (Paragraph 12.2).

10.2

Troubleshooting

If trouble is encountered, verify all installer connections to the
assembly and check that the CO power fuse is not blown. Also
verify all module connections and option switch settings, and
verify the modules are making a positive connection with the
shelf connector. If trouble persists, replace the suspect unit and
repeat procedures outlined. These procedures are not designed
to effect repairs or modifications. Any tests beyond those out-
lined herein, or repairs made beyond replacing a faulty unit, are
not recommended and may void the warranty.

11.

CUSTOMER & TECHNICAL SERVICES

11.1

Customer Service & Technical Assistance

If technical or customer assistance is required, contact Westell
by calling or using one of the following options:

Voice: (630) 898-2500
Voice: (800) 323-6883
email:

[email protected]

Visit the Westell World Wide Web site at http://

www.Westell.com

for additional information about Westell.

11.2

Part Numbers

This equipment is identified by a product number (B90-
311610), which consists of three parts: the issue letter of the
equipment (B), the assembly type (90), and the specific model
number (311610). When a change is made to the product which
changes the form, fit, or function of the product, the issue letter
is incremented by one. Please indicate the issue level as well as
the model number when making equipment inquiries.

12.

WARRANTY & REPAIRS

12.1

Warranty

Westell warrants this product to be free of defects at the time of
shipment. Westell also warrants this product to be fully func-
tional for the time period specified by the terms and conditions
governing the sale of the product. Any attempt to repair or
modify the equipment by anyone other than an authorized Wes-
tell representative will void the warranty.

12.2

Repair and Return

Westell will repair or replace any defective Westell equipment
without cost during the warranty period if the unit is defective
for any reason other than abuse, improper use, or improper
installation. Before returning the defective equipment, first re-
quest a Return Material Authorization (RMA) number from
Westell. Once an RMA number is obtained, return the defective
unit, freight prepaid, along with a brief problem description, to:

Westell, Inc.
ATTN: R.G.M. Department
750 N. Commons Drive
Aurora, IL 60504-7940

Replacements will be shipped in the fastest manner consistent
with the urgency of the situation. Westell will continue to repair

Summary of Contents for 3116-10 Issue B

Page 1: ...code and removed the previous Paragraph 4 2 This practice re flects the Issue B equipment which provides the following improvements Manufacturability PM storage increased to 90 days Event log increas...

Page 2: ...NPRM or SPRM reports in the Data Link per ANSI T1 403 1998 On board test pattern generator Notepad craft screen for documenting information about the circuit User configurable alarm threshold craft s...

Page 3: ...nd can be either a positive or negative ground refer ence This allows the NIU to operate from 24Vdc supplies at certain wireless and PCS Personal Communication Service sites In the local power mode th...

Page 4: ...15 dB 0 dB 7 5 dB AB15 dB AB22 5 dB Figure 5 3116 10 Detailed Block Diagram FAC to CPE Regen DIS EN 17 5 15 55 49 CT1 CR1 CPE Out CT CR CPE In 7 13 T R TP1 TP2 GND P201 SPAN LOCAL SPAN P201 LOCAL T1...

Page 5: ...s maintained The Auto binder Level circuitry constantly monitors the input lev els from the network and customer and adjusts how much additional LBO is required to keep the binder level at the neces s...

Page 6: ...it is less than four consecutive repetitions in duration or if the error rate is greater than 10 3 Function Code Type DS1 T1 Activate 11000 Unframed SF or ESF Loop Up 0001 0010 1111 1111 ESF DATA LINK...

Page 7: ...itors the DS1 signal from the CPE for customer loss of signal and upon detecting a loss will change the CPE LED to red and cause the unit to enter Loopback toward the network When the signal from the...

Page 8: ...3 2 2 Both AIS CI and RAI CI are backwards compatible with existing network devices and will appear as normal AIS or RAI 5 3 2 3 Upon detecting a loss of signal on the network side of the unit the uni...

Page 9: ...Circuits Craft Port The 3116 10 provides a front panel RS 232 connector for local access of performance statistics data without placing the unit into loopback See Paragraph 7 1 2 and Figure 11 6 8 PM...

Page 10: ...SU PRM NIU NPRM RPT NPRM ORB NPRM NPRM xx NPRM xx WARNING Before making any connections verify power is off including removing the fuse at the fuse and alarm panel and that any and all plug in units a...

Page 11: ...P1 will read positive with respect to TP2 A voltmeter reading of 0 6VDC equates to a 60mA span 7 1 5 Status LEDs The multi function status LEDs on the front panel provide a visual indication of variou...

Page 12: ...hat provide primary lightning protection This installation should conform to Local Codes and NEC requirements This equipment is to be installed in a restricted access location CAUTION Never apply powe...

Page 13: ...minal Setup and Operation 9 1 1 The front panel craft interface port allows the craft to configure the unit for a particular application view the stored T1 performance statistics as well as graphicall...

Page 14: ...ype C The unit is shipped from the factory with its clock set to Central Standard Time 9 2 2 2 To set the date or time use the tab to select the field then type the new parameter in the highlighted bo...

Page 15: ...lly time out 24 hours after initial activation Loopback Mode Normal Unit loops up to normal inband Data Link loopback codes p Addressed Unit loops up to unique 16 bit addressed loopback code Circuit I...

Page 16: ...c to go back to main menu Figure 19 Event Alarm Log Screen Typical Sample Only Westell B90 311610 CLEI T1L8AC0AAA EVENT ALARM LOG No Date Time Event 1 15 of 200 1 2 28 00 13 00 00 MANUAL LOOP DOWN 2 2...

Page 17: ...nt Alarm Log screen type L while in the Main Menu The Event Alarm Log appears To advance through the log type N next page or P previous page or Esc to return to the MAIN Menu 9 2 5 3 To clear all stor...

Page 18: ...ration or LBO parameters that have been provi sioned When different parameters are provisioned remotely or via the provisioning menu they will be reflected here 9 2 6 4 By using the Ctrl U keys simult...

Page 19: ...ll give a message asking if you want to save the new settings WARNING If the craft terminal is disconnected without saving the changes the changes will be lost unit does not save changes automatically...

Page 20: ...as follows 1 Information Report Provides all provisioning including Alarm Threshold information about the unit 2 Event Log Report Provides all provisioning information and a complete listing of all st...

Page 21: ...lty replace it with another unit op tioned identically and retest If the replacement unit appears to operate correctly the original unit may be faulty and should be returned to Westell for repair or r...

Page 22: ...Range 30 to 0 dBDSX C Port Impedance 100 Ohms 22 at 772 kHz Detectors D FAC and CPE LOS Detector Thresholds v 30 dB 150 ms E Code Detector Range 30 to 0 dBDSX F Code Detector Maximum Error Rate 10 3...

Page 23: ...MTLBO 0 1100 0100 1011 0011 C4B3 CPE to FAC 7 5 dB WSTTRMTLBO 7 5 1100 0100 1011 0100 C4B4 CPE to FAC 15 dB WSTTRMTLBO 15 1100 0100 1011 0101 C4B5 22 5 dB WSTTRMTLBO 22 5 1100 0100 1011 0110 C4B6 AB15...

Page 24: ...CI ON Idle on CPE LOS 2400 RAI CI ON AIS CI on CPE LOS Framing Conversion WSTFCNV DIS 1100 0101 1100 0000 C5C0 200 Frame conversion disabled g ENA C5C0 400 Frame conversion enabled Real Time Mode WST...

Page 25: ...0000 C5F0 1100 Normal Mode p Query ADDR C5F0 2100 Addressed Mode Function Code Sequence Hex C d Bit Error Responses and dB Levels q Code BER Level BER Level BER Level BER Level CPE Level Query 1100 0...

Page 26: ...optnm optstg cr lf List of Options This is a comprehensive list of command line options Simply use the codes identified in the columns below when configuring command lines OPTION OPTNM OPTSTG Monitore...

Reviews: