Page 18 of 24
PAM-190-P-A/I
5.3.2
LIM (Signal monitoring)
Command
Parameters
Unit
Group
LIM
X
x= 0… 2000
0,01 %
EXP
This command defines the pressure, which corresponds to 100 % of the input signal. If the demand is set
incorrectly, this leads to incorrect system settings, and the dependent parameters cannot be calculated
correctly.
Example:
LIM 500 (5% lower/upper limitation)
If the input signal gets higher than 95 % or lower than 5%, it leaves the permitted range and the output will
switch off.
5.3.3
R (Command signal ramp time)
Command
Parameter
Unit
Group
R:I
X
i= UP|DOWN
x= 50… 10000
ms
STD
Two quadrant ramp function.
The ramp time is separately set for UP and DOWN ramps.
t
A
u
sg
a
n
g
/O
u
tp
u
t A
A:UP
A:DOWN
0%
working
range
error range for
unipolar signals
100%