PArA
Cntr
Name Value range
Description
Your
value
Pb1
1...9999
proportional band 1 [phys]
Pb2
1...9999
proportional band 2 [phys]
ti1
off, 1...9999 integral action 1 [s]
ti2
off, 1...9999 integral action 2 [s]
td1
off, 1...9999 derivative action 1 [s]
td2
off, 1...9999 derivative action 2 [s]
t1
0,4...9999
min. cycle time 1 [s]
t2
0,4...9999
min. cycle time 2 [s]
SH
0..9999
neutral zone [phys]
d.SP
-1999...9999 additional contact D / Y [phys]
tP
off, 0.1...9999 min. pulse length [s]
tt
3...9999
motor travel time [s]
Y2
-100...100
correcting variable 2
Y.Lo
-105..105
lower output range [%]
Y.Hi
-105...105
upper output range [%]
Y.0
-105...105
working point [%]
Ym.H
-100...100
max. mean value [%]
L.Ym
1...9999
max. deviation mean [phys]
oFFS
-120...120
ratio offset
tEmP
0...9999
probe temperature
SEtP
Name Value range Description
SP.LO
-1999...9999 lower setpoint range [phys]
SP.Hi
-1999...9999 upper setpoint range [phys]
SP.2
-1999...9999 2nd setpoint [phys]
r.SP
off,0.01...9999 setpoint ramp [/min]
t.SP
0.0...9999
timer dwell time [min]
ProG
Name Value range Description
SP.01
-1999...9999 target setpoint 1
Pt.01
0.0...9999 segment time 1 [min]
SP.02
-1999...9999 target setpoint 2
Pt.02
0.0...9999 segment time 2 [min]
SP.03
-1999...9999 target setpoint 3
Pt.03
0.0...9999 segment time 3 [min]
SP.04
-1999...9999 target setpoint 4
Pt.04
0.0...9999 segment time 4 [min]
InP.1
,
InP.2
Name Value range Description
InL.1
(InL.2)
-1999...9999 lower input value [phys]
OuL.1
(OuL.2)
-1999...9999 lower output value [phys]
InH.1
(InH.2)
-1999...9999 upper input value [phys]
OuH.1
(OuH.2)
-1999...9999 upper output value [phys]
t.F1
(t.F2)
0...999,9
filter time [s]
E.tc1
(E.tc2)
OFF, 0...100 external TC[°C]
Lim
Name Value range
Description
L.1
off, -1999...9999 lower limit 1 [phys]
H.1
off, -1999...9999 upper limit 1 [phys]
HYS.1
0...9999
hysteresis 1 [phys]
L.2
off, -1999...9999 lower limit 2 [phys]
H.2
off, -1999...9999 upper limit 2 [phys]
HYS.2
0...9999
hysteresis 2 [phys]
L.3
off, -1999...9999 lower limit 3 [phys]
H.3
off, -1999...9999 upper limit 3 [phys]
HYS.3
0...9999
hysteresis 3 [phys]
HC.A
0...9999
heat current limit [A]
ConF
Cntr
Name Value
range
Description
SP.Fn
setpoint processing
0
Setpoint/ ext. Setpoint
1
program controller
2
timer mode 1
3
timer mode 2
4
timer mode 3
5
timer mode 4
6
timer mode 5
7
timer mode 6
8
st SP-E
9
prog SP.E
b.ti
0...9999
timer tolerance
C.tYP
process value processing
µ
0
process value = x1
1
ratio controller (x1+oFFS)/x2
2
difference (x1 - x2)
3
max (x1, x2)
4
min (x1, x2)
5
mean value (x1, x2)
6
Switch-over (x1, x2)
7
Oxygen measurement with const. probe
temperature
8
Oxygen measurement with measured
probe temperature
C.Fnc
control behaviour
0
signaller (on/off controller)
1
PID controller (2-point and continuous)
2
D/Y switch-over
3
2 x PID (3-point and continuous)
4
3-point stepping controller
mAn
automatic/manual switching
0
Manual operation not permitted
1
Manual operation admitted
C.Act
direction of operation
0
inverse, e.g. heating
1
direct, e.g. cooling
FAIL
behaviour at sensor break
0
outputs off
1
switch to Y2
2
mean correcting value
rnG.L
lower control range [phys]
rnG.H
upper control range [phys]
InP.1
,
InP.2
Name Value
range
Description
I.Fnc
function
0
no function
1
heating current input
2
External setpoint
4
2nd process value X2
6
no controller input
7
process value X1
S.tYP
sensor type
0
Thermocouple type L (-100...900°C),
Fe-CuNi DIN
1
Thermocouple type J (-100...1200°C),
Fe-CuNi
2
Thermocouple type K (-100...1350°C),
NiCr-Ni
3
Thermocouple typeN (-100...1300°C), Ni-
crosil-Nisil
4
Thermocouple type S (0...1760°C),
PtRh-Pt10%
5
Thermocouple type R (0...1760°C),
PtRh-Pt13%
6
Thermocouple type T (-200...400°C),
Cu-CuNi
7
Thermocouple type C (0...2315°C),
W5%Re-W26%Re
8
Thermocouple type D (0...2315°C),
W3%Re-W25%Re
9
Thermocouple type Typ E (-100...1000°C),
NiCr-CuNi
10 Thermocouple type Typ B
(0/100...1820°C), PtRh-Pt6%
18 special thermocouple (Linearization
necessary)
20 Pt100 (-200.0 ... 100,0 (150)°C)
21 Pt100 (-200.0 ... 850,0 °C)
22 Pt1000 (-200.0...850.0 °C)
23 Special 0...4500 Ohm (default as
KTY11-6)
24 Special 0...450 Ohm
25 Special 0...1600 Ohm
Name Value
range
Description
26 Special 0...160 Ohm
30 Current 0/4...20mA
31
Current: 0...50 mA AC (2 opto coupler
o 1 relay/hc-Inp 2 only)
40 Voltage 0...10V / 2...10 V (Inp1 only)
41 Special (-2,5...115 mV)
42 Special (-25...1150 mV)
43 Special (-25...90 mV)
44 Special (-500...500 mV)
45 Special (-5...5 V) (Inp1 only)
46 Special (-10...10 V) (Inp1 only)
47 Special (-200..200 mV)
50 Potentiometer 0...160 Ohm
51 Potentiometer 0...450 Ohm
52 Potentiometer 0...1600 Ohm
53 Potentiometer 0...4500 Ohm
4wir
Resistance connection type(only for
Inp.1)
0
3 wire connection
1
4 wire connection
S.Lin
linearization
0
no linearization
1
special linearization
Corr
measured value correction
0
no correction
1
offset correction
2
2-point correction
3
scaling
In.F
OFF,
-1999...
9999
alternative value INP
Lim1
,
Lim2
,
Lim3
Name Value
range
Description
Fnc.1
(
Fnc.2
)
(
Fnc.3
)
function of limit 1 (2, 3)
0
switched off
1
measurement value
2
measurement value with latch
Src.1
(
Src.2
)
(
Src.3
)
source of limit 1 (2, 3)
0
process value
1
control deviation
2
dev suppression
3
INP1
4
INP2
6
Setpoint
7
correcting variable
11 dev suppression without time
limit
HC.AL
heating current alarm
0
switched off
1
ov short circuit
2
break + short circuit
LP.AL
loop alarm
0
no LOOP alarm
1
LOOP alarm active
Out.1
,
Out.2
,
Out.3
Name Value
range
Description
O.tYP
type of OUT (only Out.3 - analog)
µ
0
relay/logic
1
0 ... 20 mA continuous
2
4 ... 20 mA continuous
3
0 ... 10 V continuous
4
2 ... 10 V continuous
5
transmitter supply
O.Act
direction of operation
0
direct
1
inverse
Y.1
controller output Y1
0
not active
1
active
Y.2
controller output Y2
0
not active
1
active
Lim.1
signal limit 1
0
not active
1
active
Lim.2
signal limit 2
0
not active
1
active
Lim.3
signal limit 3
0
not active
1
active
LP.AL
loop alarm
0
not active
1
active
Name Value
range
Description
HC.AL
heating current alarm
0
not active
1
active
HC.SC
SSR short circuit
0
not active
1
active
timE
timer run
0
not active
1
active
P.End
program end
0
not active
1
active
FAi.1
signal INP1 fail
0
not active
1
active
FAi.2
signal INP2 fail
0
not active
1
active
Sb.Er
Message system bus - error
0
not active
1
aktive
Out.0
-1999
...9999
scaling 0% (only for Out.3 analog)
µ
Out.1
-1999
...9999
scaling 100% (only for Out.3 analog)
µ
O.Src
signal source (only for Out.3 analog)
µ
0
not akctive
1
controller output y1 (cont.)
2
controller output y2 (cont.)
3
process value
4
Effective setpoint
5
control deviation
7
INP1
8
INP2
O.FAI
fail behaviour
µ
0
upscale
1
downscale
LOGI
Name Value
range
Description
di.Fn
function of inputs
0
direct
1
inverse
2
toggle key function
L_r
block front
0
interface only
1
always on
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
SP.2
2nd setpoint
0
interface only
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
SP.E
external setpoint
0
interface only
1
always on
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
Y2
2nd actuator value
0
interface only
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
mAn
automatic/manual switching
0
interface only
1
always on
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
C.oFF
controller off
0
interface only
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
Name Value
range
Description
Err.r
Reset error list
0
interface only
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
P.run
program run/stop
0
interface only
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
I.ChG
switchover Inp1./ Inp2
0
interface only
2
di1 switches
5
Func switches
7
limit 1 switches
8
limit 2 switches
9
limit 3 switches
othr
Name Value
range
Description
bAud
baudrate
µ
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
4
38400 Baud
Addr
1...247
address
µ
PrtY
parity
µ
0
No parity, 2 stop bits
1
even parity
2
odd parity
3
No parity, 1 stop bit
dELY
0...200
response delay [ms]
µ
S.IF
system interface
µ
0
not active
1
active
D.Unt
display unit
0
no unit
1
temperature unit (see Unit)
2
O2 unit (see O2)
3
%
4
bar
5
mbar
6
Pa
7
kPa
8
psi
9
l
10 l/s
11 l/min
12 Ohm
13 kOhm
14 m
15 A
16 mA
17 V
18 mV
19 kg
20 g
21 t
22 Text of physical unit
O2
parameter unit for O2
µ
0
Parameter in ppm with O2 function
1
Parameter in % with O2 function
Unit
unit
1
°C
2
°F
3
Kelvin
dP
decimal points
0
0 digits behind the decimal point
1
1 digits behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
C.dEL
0..200
modem delay [ms]
µ
Optional
+
Depending on equipment version and the configuration
unused parameters are faded out.
Universal Regler / controller KS 45
Seite / page 2