62 | CFW700
Technical Specifications
E
ng
lis
h
8 TECHNICAL SPECIFICATIONS
8.1 POWER DATA
Power Supply:
Maximum rated voltage: 240 V for 200...240 V models, 230 V for 220 / 230 V models and
480 V for 380...480 V models and 600 V for 500...600 models up to 2000 m height. It is
necessary to apply 1.1 % voltage derating every 100 m (328 ft) above 2000 m (6562 ft),
limited to 4000 m (13123 ft).
Remaining specifications according to user’s manual.
Voltage tolerance: -15 % to +10 % of the nominal voltage.
Frequency: 50 / 60 Hz (48 Hz to 62 Hz).
Phase imbalance: ≤3 % of the rated phase-to-phase input voltage.
Overvoltage according to Category III (EN 61010/UL 508C).
Transient voltage according to Category III.
Maximum of 60 connections per hour (1 per minute).
Efficiency: according to class IE2 as per EN 50598-2.
Typical input power factor:
- 0.94 for three-phase power supply models in the rated conditions.
- 0.70 for single-phase power supply models in the rated conditions.
- cos
ϕ
(displacement factor): > 0.98.
Refer to
APPENDIX B - TECHNICAL SPECIFICATIONS on page 218
for more information
about the technical specifications.
Summary of Contents for CFW700 Series
Page 3: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 10: ......
Page 13: ......
Page 14: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 61: ......
Page 64: ......
Page 66: ......