High-Performance Distance Sensor
9
Outputs
Analogue Output
The analogue output is connected to analogue earth. The analogue output can be configured as a current
output or a voltage output. If you have the choice we recommend the use of the voltage output (reduced cur-
rent consumption).
The analogue output reads out a standard signal of 0...10 V when configured as a voltage output (see settings).
The analogue output reads out a standard signal of 4...20 mA when configured as a current output (see settings).
Error Outputs
The PNP error output is switched to positive if no object is detected within the selected working range, or if an
error has occurred (e.g. an interrupted conductor at the current output). The red F LED lights up to indicate that
the error output has been activated.
RS-232 interface
This sensor is equipped with an RS-232 interface for communication with a device such as PC or a controller.
Sensor functions can be activated, and scanning results can be acquired via the RS-232 interface.
7. Adjustment
7.1. Manual Adjustments
Reset:
• Set the rotary selector switch
Ý
to
RESET
• Briefly press the minus-key
or the plus-key
è
red F-LED lights up
è
Delivery status restored (RES. MODE, rising characteristic function, full measuring range, filter func-
tion off.) The adjusted transmission speed (Baud rate) and the setting Current or Voltage Output is not
changed by the
RESET
.
• Set the rotary selector switch
Ý
to
RUN