- 25 -
Installation manual
M-WRG-M/MB-FK1 / FK2
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L AT I O N & H E AT R E C O V E R Y
Outer wall terminal
Excess
Stainless steel pod, M-WRG-ES
5 - 10 mm from the plastered external wall
Stainless steel pipe set, M-WRG-ESR 25 - 30 mm from the plastered external wall
Stainless steel louvred design
(surface-mount) M-WRG-ESG/AP
5 - 10 mm from the plastered external wall
Stainless steel louvred design
(flush-mount) M-WRG-ESG/UP
5 - 10 mm from the unplastered external wall,
depending on the layer structure
Tab. 3:
Excess length of the ventilation pipes from the external wall
►
Remove the ventilation pipes from the openings in the wall box.
►
Shorten the ventilation pipes to the marked length.
►
Deburr the inner and outer ends of the ventilation pipes.
NOTE
If you do not deburr the ventilation pipes there is a risk of damaging the seals at the ventilation unit
and outer wall terminal.
9.18
Inserting and fixing the ventilation pipes
►
Apply permanently elastic sealant to the
outer skin of the ventilation pipes (item 1 in
►
Push the ventilation pipes back into the
openings in the wall box.
►
Twist the two ventilation pipes into the
openings in the wall box until they end flush
(item 2 in Fig. 29).
Fig. 29: Inserting and fixing ventilation pipes