~ - 10 - ~
9
CUR: Charging current (option)
10A
(300W )
20A
(600W
~3500W)
0 ~ 60A
10
IECO: I
nverter no-load ECO mode
Note: If select
“Y”, check whether
the configured load rate in
“ Inverter shutdown load rate” is
correct or not, if not, change it.
(option)
N
Y / N
11
INLS:
Inverter no-load shutdown
function
Note: If select
“Y”, check whether
the configured load rate in
“ Inverter shutdown load rate” is
correct or not, if not, change it.
(option)
N
Y / N
12
INLS:
Setting of the load rate of
UPS
a
uto-shutdown
,
The load rate
of shutdown needed on the scene
shall prevail during application.
(Shall be taken as valid only when
DC supply power)
(option)
3 %
3 % ~ 50 %
13
INLS:
Setting of the delay time of
UPS
a
uto-shutdown
,
When load
≤
setting
value
, the system will shut
down after the configured time.
(Shall be taken as valid
only in
battery mode
)
(option)
1 min
1 ~ 99 min
14
ACAU:
AC self-starting function
(option)
Y
Y / N
15
DCAU:
DC auto restart function
Note: If select
“Y”, check whether
the configured time in
“DC auto
restart time
” is correct or not, if not,
change it. (option)
N
Y / N