
_______________________________________________________________________________________________________________________________
7 Preparing the appliance for use
Merrychef conneX Installation and User Manual
38
_______________________________________________________________________________________________________________________________
6.3
Electrical installation requirements
Circuit Breakers (MCB ~ Miniature Circuit Breakers)
For overcurrent protection, a Type ‘D’ circuit breaker (designed specifically for this
type of equipment) must be fitted, as a
recommend alternative a higher rated type ‘C’ type breaker can be used (see below). Establishments with standard (Type ‘B’)
circuit breakers are sensitive to ‘surges’ which occur on switching on freezers, refrigerato
rs and other catering equipment,
including microwave combination ovens. An individual, suitably rated overcurrent circuit breaker should be fitted for each
appliance installed, along with a separate dedicated Residual Current Device (Ground Fault Circuit Interrupter).
Model
Recommended Circuit Breaker
(per phase)
Alternative Recommended
Circuit Breaker (per phase)
ConneX 12 standard power
D16
C20
ConneX 12 high power/conneX 16 - 1 phase
D32
C40
ConneX 12 high power/conneX 16 - 3 phase
D16
C20
Residual-current device (RCD)
The installation regulations require protection by a Residual Current Device (Ground Fault Circuit Interrupter). Suitable residual
current devices, with a high immunity to nuisance tripping, meeting the relevant national regulations must be used. As long
cable runs can be a factor in nuisance tripping, they should be avoided.
If the installation includes more than one appliance, one residual-current (GFCI) device must be provided for each appliance.
Low impedance electrical supply
This commercial combination microwave oven complies with EN 61000-3-11. However, when connecting sensitive
equipment to the same supply as the appliance, the user should determine in consultation with the supply authority, if
necessary, that a low impedance supply is used.
Electrical supply
Illustration
Phase
Meaning
Single
phase
UK 13A models are fitted with a moulded plug to BS1363, fused at
13A.
EU 16A models are fitted with a moulded plug to CEE 7/7 (Type F
Schuko) rated at 16A
30A models are fitted with a blue 32A plug to IEC 60309 (EN
60309).
Connected to a dedicated RCD (GFCI) protected supply, with
appropriate circuit breaker as detailed above.
Twin
phase
Twin phase models should be connected as shown (the twin
phase oven requires a three phase supply, utilising L1 & L2 as two
separate single phases, L3 is not used).
30A models are fitted with a red 32A plug to IEC 60309 (EN
60309).
EU 16A models are fitted with a red 16A 90
o
plug to IEC 60309 (EN
60309).
Connected to a dedicated RCD (GFCI) protected supply, with
appropriate circuit breaker as detailed above.
Single
phase
60Hz
(two pole)
Single phase models, utilising L1 & L2 split phase supply (240V) or
L1 & L2 from a three phase supply (208V). Neutral is not used.
15A models are fitted with HBL5666C NEMA 6-15P & 15A
HBL4570C NEMA L6-15P plugs.
20A models are fitted with a HBL5466C NEMA 6-20P plug.
30A models are fitted with YP-91L NEMA 6-30P & HBL2621 NEMA
L6-30P plugs.
Connected to a dedicated RCD (GFCI) protected supply, with
appropriate circuit breaker as detailed above.
Please refer to electrical installation data for other country specific models.
L1
L2