![Weishaupt WM-L20/2-A R Manual Download Page 29](http://html.mh-extra.com/html/weishaupt/wm-l20-2-a-r/wm-l20-2-a-r_manual_953367029.webp)
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
5 Installation
83252902 1/2019-09 La
29-84
Connect oil supply and observe:
do not twist oil hoses
avoid mechanical tension
consider length of hose required for the hinge range,
do not kink oil hoses (curve radius
1
of 145 mm must be maintained).
If these conditions for connection can not be met:
Adapt oil supply on site.
1
Purge oil supply and ensure it is tight
CAUTION
Damage to oil meter in oil circulating device resulting from purging
If an oil circulating device is fitted, the purging process could damage the integ-
rated oil meter.
Replace oil meter with adapter during purging.
CAUTION
Oil pump seized due to running dry
Pump could be damaged.
Fill oil supply with oil and purge.
Ensure oil supply is tight.