Installation and operating instruction
Oil burner WL40Z-A 1LN
4 Installation
83298902 2/2019-05 La
22-112
4.3 Burner installation
Pay attention to local regulations for lifting and carrying loads [ch. 3.4.8].
Remove screws
1
.
Remove pin
4
.
Remove burner flange
3
from burner housing.
It is possible to install the burner rotated by 180 if space is limited. This requires
conversion measures [ch. 4.3.1].
Fit flange gasket
5
and burner flange
3
to the boiler using screws.
The aperture between combustion head and refractory should be filled with
flame-proof, resilient insulating material. Do not make solid.
Unplug ignition cables
6
.
Remove screw
7
and remove diffuser
8
.
Undo screw
2
and remove ignition electrode holder.
Fit nozzle [ch. 9.4].
Re-fit diffuser and ignition cables.
Set ignition electrodes [ch. 9.6]
Check nozzle distance and adjust if necessary [ch. 9.8].
Push burner on to the stay bolts of the burner flange.
Re-fit pin
4
.
Hinge burner closed and secure with screws
1
.
2
8
7
3
4
5
6
1