Installation and operating instruction
Room device WEM-RG1
5 Operation
83310002 1/2017-11 La
15-20
5.8 Service level
5.8.1 Check assignment
The heating circuit to which the room device is assigned can be displayed with
parameter
0F
.
Press Manual operation
and Automatic operation
simultaneously for ap-
prox. 2 seconds.
The service level is activated.
Press dial knob.
The address of the heating circuit accessed is displayed.
The assignment can be changed using the display and operating unit of the con-
densing boiler.
The standard display re-appears after approx. 30 seconds.
5.8.2 Adjusting the room temperature
If no optimal placement of the room device is possible or a measurement error is to
be compensated, the measured room temperature can be adjusted.
Setting range: -5.0 ... 5.0 K
Factory setting: 0.0
Press Manual operation
and Automatic operation
simultaneously for ap-
prox. 2 seconds.
The service level is activated.
Turn dial knob until parameter
1F
is displayed.
Press dial knob.
Current room senor adjustment is displayed flashing.
Set and confirm adjustment required using the dial knob.
The value has been saved.
The standard display re-appears after approx. 30 seconds.