Additional parameters that are available while logged in as Management include:
Reset Filter
– The
Reset Filter
is an interval of time, in milliseconds (rounded down to the nearest 5 ms). One condition for a reset
is that the wellhead pressure must be below the reset pressure for
Reset Filter
.
Pop Off Filter
–
Pop-off Filter
is an interval of time, in milliseconds (rounded down to the nearest 5 ms). If the wellhead pressure
stays above the
Pop-Off Setpoint
for
Pop-off Filter,
the system triggers a pop-off.
Minimum Popoff Time
– The minimum interval of time in milliseconds that the valve remains in the open/relief state once a pop-
off occurs. A reset will not occur until this interval of time has elapsed after a pop-off or manual dump.
4.1.2 Weir
The
Weir
account allows the user access to the same settings as the Management account but allows values that are for system test
mode only. Access to the Weir account is not required for operation of the system. Once logged in, the user icon displays a
W
confirming the user is currently logged in as
Weir
.
4.2 Changing Account Password
The password for any account can only be changed if the current user is logged in with administrative privileges. Once logged in as an
administrator, the password can be changed by clicking the user icon in the top right corner of the screen and selecting the
Change
Password
option.