Weinzierl KNX IP BAOS 774 Operation And Installation Manual Download Page 5

©

2019 WEINZIERL ENGINEERING GmbH 

page 5/5

 

6 Bit 
7 Bit 
1 Byte 
2 Byte 
3 Byte 
4 Byte 
6 Byte 
8 Byte 
10 Byte 
14 Byte 
 
The data point type descriptions can be found in the download 
area of the KNX Association (

www.knx.org

). 

Parameter

 

The device has 1000 bytes available for user defined parameters 
which can be accessed via the BAOS protocol. 

 

Parameter Byte

 

For each of the parameter bytes a value between 0 and 255 can 
be entered. 

Programming 

The KNX IP BAOS 774 can be programmed in different ways by 
the ETS: 

Via KNX Bus 

The device only needs to be connected to the KNX bus. The 
ETS requires an additional interface (for example, USB) to have 
access to the bus. Via this way both the individual address and 
the entire application including IP configuration can be pro-
grammed. Programming via the bus is recommended if no IP 
connection can be established. 

Via KNXnet/IP Tunneling 

No additional interface is required. Programming via KNXnet/IP 
Tunneling is possible if the device already has a valid IP configu-
ration (e.g. via DHCP). In this case the device is displayed in the 
interface configuration of the ETS and must be selected. The 
download is executed via the ETS project as with many other 
devices. 

Via direct IP connection 

While KNXnet/IP Tunneling and is limited to the speed of KNX 
TP the device can be loaded via a direct IP connection at high 
speed. The direct IP connection is possible if the device already 
has a valid IP configuration as well as an individual address. To 
do this select "Use direct IP connection if available" in the ETS 
menu "Bus 

– Connections - Options". The download is then 

directly performed in the device and is not visible in the ETS 
group monitor. 

  

Due to the significantly shorter transmission times it is 
recommended to perform downloads via IP. 

 

 

 

 

 

       WARNING 

 

 

The device must be mounted and commis-
sioned by an authorized electrician. 

 

The prevailing safety rules must be heeded. 

 

The device must not be opened. 

 

For planning and construction of electric in-
stallations, the relevant guidelines, regulations 
and standards of the respective country are to 
be considered. 

 

 

 

ETS4/5 Database 

www.weinzierl.de/en/products/774/ets4 

Datasheet 

www.weinzierl.de/en/products/774/datasheet

 

CE Declaration 

www.weinzierl.de/en/products/774/ce-declaration

 

Weinzierl Engineering GmbH

 

D-84508 Burgkirchen / Alz 

Germany 

www.weinzierl.de 

[email protected] 

 

2019/03/06

 

 

Summary of Contents for KNX IP BAOS 774

Page 1: ...connect e g control or visualization tools to KNX The KNX IP BAOS protocol is available in the following versions KNX IP BAOS Binary V2 A binary protocol that is espe cially suitable for small microcontroller KNX IP BAOS Web Services A URL based protocol with JSON syntax Protocol descriptions can be downloaded at the KNX IP BAOS 774 product site at www weinzierl de KNX IP BAOS 774 as application s...

Page 2: ...oject See the ETS database section for more information As factory default the assignment of the IP address is set to automatically via DHCP and thus no further settings are neces sary To use this feature a DHCP server on the LAN must exist e g many DSL routers have an integrated DHCP server After connecting the KNX IP BAOS to the LAN and the KNX bus it should automatically appear in the ETS withi...

Page 3: ...f the text field frame switches to color red after entering the address the address is already taken within your ETS project Make sure that none of the addresses above are already present in your KNX installation By clicking on the KNX IP BAOS 774 device entry within your ETS projects topology view an information column Properties will appear on the right side of the ETS window Within the Set ting...

Page 4: ...tons and This feature can be enabled and disabled via the parameter Prog mode on device front The recessed programming button next to the Programming LED is always enabled and not influenced by this parameter Manual operation on device This parameter sets the duration of the manual mode Upon completion the normal display mode is restored Sending of Indications When this parameter is activated a cl...

Page 5: ...onfiguration of the ETS and must be selected The download is executed via the ETS project as with many other devices Via direct IP connection While KNXnet IP Tunneling and is limited to the speed of KNX TP the device can be loaded via a direct IP connection at high speed The direct IP connection is possible if the device already has a valid IP configuration as well as an individual address To do t...

Reviews: