IP address 

Here the IP address of the KNX IP Router 752 

secure

 can be 

entered. This is used to address the device via the IP network 
(LAN). The IP addressing should be coordinated with the admin-
istrator of the network. 

Subnet mask 

Enter the subnet mask here. The device uses the values entered 
in this mask to determine whether there is a communication 
partner in the local network. If there is no partner in the local 
network, the device will not send the telegrams directly to the 
partner but to the gateway that routes the telegram. 

Default gateway

 

Enter the IP address of the gateway here, e.g. the DSL router of 
the installation. 

Routing Multicast Address 

This address is used for routing telegrams on IP. The multicast 
IP address 224.0.23.12 was reserved (KNXnet/IP) at the IANA 
(Internet Assigned Numbers Authority) for this purpose. If a 
different multicast IP address is required, it must be within the 
range of 239.0.0.0 to 239.255.255.255. 

 

Example of assigning IP addresses 

A PC is to be used to access the KNX IP Router 752 

secure

 
IP address of the PC: 

192.168.1.30 

Subnet of the PC:   

255.255.255.0 

The KNX IP Router 752 

secure

 is located in the same LAN, i.e. it 

uses the same subnet. The subnet constrains the IP addresses 
that can be assigned. In this example, the IP address of the KNX 
IP Router must be 192.168.1.xx, where xx can be a number from 
1 to 254 (with the exception of 30, which is already taken by the 
client PC). It must be ensured that no IP addresses are assigned 
twice. 

IP address of the KNX IP Router 

192.168.1.31 

Subnet of the KNX IP Router:  

255.255.255.0 

 

Remote access 

Remote access via Internet is possible with the KNX IP Router 
752 

secure

. More details can be found in the document "Remote 

access with the ETS" at www.weinzierl.de 

 

ETS parameter dialogue 

The following parameters can be set using the ETS.

 

General settings 

 

Prog. mode on device front 

In addition to the normal programming button 

 the device 

allows activating the programming mode on the device front 

without opening the switchboard cover. The programming mode 
can be activated and deactivated via pressing simultaneously 
both buttons 

 and 

.  

This feature can be enabled and disabled via the parameter 
“Prog. mode on device front”. The recessed programming button 

 (next to the Programming LED 

) is always enabled and 

not influenced by this parameter.  

Manual operation on device

 

This  parameter  sets  the  duration  of  the  manual  mode.  Upon 
completion the normal display mode is restored. 

 
Routing (KNX -> IP) 

 

 

Group telegrams (main group 0 to 13) 

Block:

 

No group telegrams of this main group are 
routed to IP. 

Route:

 

All group telegrams of this main group are 
routed to IP independent of the filter table. 
This setting is for test purposes only. 

Filter:

 

The filter table is used to check whether or 
not the received group telegram should be 
routed to IP. 

Group telegrams (main group 14 to 31) 

Block:

 

No group telegrams of main groups 14 to 31 
are routed to IP. 

Route:

 

All group telegrams of main groups 14 to 31 
are routed to IP. 

Filter:

 

The filter table is used to check whether or 
not the received group telegram should be 
routed to IP. 

Individually addressed telegrams  

Block:

 

No individually addressed telegrams are 
routed to IP. 

Route: 

All individually addressed telegrams are 
routed to IP. 

Filter:

 

The individual address is used to check 
whether the received individually addressed 
telegram should be routed to IP. 

Broadcast telegrams 

Block:

 

No received broadcast telegrams are routed 
to IP. 

Route:

 

All received broadcast telegrams are routed 
to IP. 

Acknowledge (ACK) of group telegrams 

Always:

 

A acknowledge is generated for every re-
ceived group telegram (from KNX). 

Only if routed:

 

A acknowledge is only generated for re-
ceived group telegrams (from KNX) if they 
are routed to IP. 

Summary of Contents for 5249

Page 1: ... and send valid telegrams A time stamp in the routing telegram ensures that no previously recorded telegrams can be replayed This prevents the so called replay attack The key for the routing communication is reassigned by ETS for each installation If KNX IP Security is used for routing all con nected KNX IP devices must support security and be configured accordingly KNX IP Security for the interfa...

Page 2: ...upler If the individual address is in the form of x y 0 x y 1 15 the router operates as a line coupler If it is in the form of x 0 0 x 1 15 the router acts as a backbone coupler Switch LAN KNX IP Router 752 secure 1 0 0 KNX IP Router 752 secure 2 0 0 KNX TP 1 1 0 1 2 0 1 2 1 1 2 6 1 2 5 1 2 4 1 2 3 1 2 2 1 1 1 1 1 6 1 1 5 1 1 4 1 1 3 1 1 2 KNX TP 2 1 0 2 2 0 2 2 1 2 2 6 2 2 5 2 2 4 2 2 3 2 2 2 2 1...

Page 3: ...indications of the IP LED For testing purposes for example during commissioning the configured routing settings filter or block can be bypassed via manual operation With the button Pass GAs the forwarding of group addressed telegrams can be activated With the button Pass IAs the forwarding of individually ad dressed telegrams can be activated This is visualized with a single flash of the Mode LED ...

Page 4: ...ace function the device contains additional individu al addresses that can be set in the ETS When a client e g ETS sends via the KNX IP Router telegrams to the bus they contain a sender address as one from the additional addresses Each address is associated with a connection Thus response telegrams can be clearly transmitted to the respective client The additional individual addresses must be sele...

Page 5: ...dresses for the interface connections are displayed in the topol ogy view Each individual KNX address can be changed by clicking on the list entry and typing in the desired address into the Individual Address text field If the text field frame switches to color red after entering the address the address is already taken within your ETS project Make sure that none of the addresses above are already...

Page 6: ...nzierl de ETS parameter dialogue The following parameters can be set using the ETS General settings Prog mode on device front In addition to the normal programming button the device allows activating the programming mode on the device front without opening the switchboard cover The programming mode can be activated and deactivated via pressing simultaneously both buttons and This feature can be en...

Page 7: ...whether the received group telegram should be routed to KNX Group telegrams main group 14 to 31 Block No group telegrams of main groups 14 to 31 are routed to KNX Route All group telegrams of the main groups 14 to 31 are routed to KNX Filter The filter table is used to check whether the received group telegram should be routed to KNX Individually addressed telegrams Block No individually addressed...

Page 8: ...rm downloads via IP Open Source Licenses This product contains open source software license curve25519 donna Curve25519 elliptic curve public key func tion Source http code google com p curve25519 donna Copyright 2008 Google Inc All rights reserved Redistribution and use in source and binary forms with or with out modification are permitted provided that the following condi tions are met Redistrib...

Reviews: