Caution 
Emergency 
Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using an 
MT-600/8000 to comply with ICS Safety Recommendations. 

 

51

Supply Voltage 

Caution 

52

Condition 

Do not power the MT-600/8000 and inductive DC loads

, or input circuitry 

to the controller, with the same power supply. Note: The 24 VDC output 
from some controllers may not have enough current to power the 
MT-600/8000. 

 

Caution  

53

Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 
1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot or 
signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 
suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 
signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 
earth ground. This provides a path for static and high frequency dissipation. 
Typical values to use are 1MOhm and 4700pF. 
To prevent the HMI from becoming damaged or having sound output issues, 
after turning the device off, please wait 10 seconds before turning the device 
on again. 

 
 

C
 

aution  

54

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 
turn the connector screw counterclockwise until the gap is wide open, insert 
the wire all the way in, and turn the screw clockwise until it’s tight. 
Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 
‘0V‘ terminal. 

12

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

 

 

 

13

2.2.3 CE Requirements 

 
To make an MT-600/8000 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 
power connector. This ground connection should be run directly to the central star earth connection 
point (as recommended in most Installation Instructions). 

 

14

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 

Considerations 

57

WARNING! 

The system designer should be aware that devices in Controller systems could 
fail and thereby create an unsafe condition. Furthermore, electrical 
interference in an operator interface, such as an MT-600/8000, can lead to 
equipment start-up, which could result in property damage and/or physical 
injury to the equipment operator. 

3

 

Summary of Contents for MT-6056i

Page 1: ...s has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 1 2 0 Installation Inst...

Page 2: ...splays Make sure that the displays are installed correctly and that the operating limits are followed See Specifications z Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install these...

Page 3: ...al 1 2 2 2 2 Grounding Requirements Chassis ground must be used DC ground is not directly coupled to Earth ground internally It is preferable not to ground DC negative return to chassis ground as poor site earths can introduce noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as sho...

Page 4: ...dards To conform with ICS Safety Recommendations checks should be place in the controller to ensure that all writable registers that control critical parts of plant or machinery have limit checks built into the program wit Programming C an out of lim 3 304 81 Safety Recommendations Consid controller Where the operator is exposed to the machinery such as in loading or unloading a machine tool or wh...

Page 5: ...0 to download projects from PC by the USB 2 0 client port Support USB 2 0 client interface The cable regulation must accord with HI SPEED USB Revision 2 0 SHIELDED How to install USB driver of HMI i series It is necessary to install USB driver of HMI on PC before at the first time enjoying this function The HMI models MT6050i MT6056i MT6070iH MT6100i MT8070iH and MT8100i 1 Using USB cable mini sid...

Page 6: ...een parameter will be stored in Flash er Rom z If losing or forgetting system passwords users can set Dip Switch 1 to ON position the rest of Dips remain on OFF position and then reboot MT8000 series Under this situation MT8000 series will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired restoring the sy...

Page 7: ... misuse including but not l b imit to incorrect set up and wiring current leakage from machine platform and incorrect input power modified in any way 3 0 Specifications Hardware Specification Display 5 6 TFT LCD Brightness 300 cd m2 Color 65 s r 536 colo Contrast Ratio 300 1 Resolution WxH dots 320 x 234 Back light LED Backlight life time avg 30 000 hr min Touch panel 4 wires resistive type Touch ...

Page 8: ...Cutout dimensions MT 6056i 192mm 7 56 W x 138mm 5 43 H Front View Rear View Bottom View a DIP SW Reset button e USB Client port b Fuse f Com1 RS232 c Power connector g Com1 RS485 d VESA 75mm screw holes GME6056I0_MT6056i_Installation_101028 8 ...

Reviews: