9

2.1.2 Making a NEMA-4 Mounting 

Panel  
Details

 

The unit can be mounted into panels with a depth of 4”(105mm).    It is recommended that 
the unit be mounted on the front panel of a steel enclosure, through an appropriate 
opening*. Allow a clearance of 1”(25mm) around the sides of the unit for mounting 
hardware. Allow clearance for cable connections to the back of the unit. Unit depth may 
vary according to cable type used. Typically, plan a depth to accommodate at least 
4”(105mm) behind the panel. 

NEMA-4 
Mounting

 

Put the unit through the panel cut out. Slide the clamps (packed with product) into the 8 
holes provided around the case. Tighten the clamping screws in an even pattern until the 
unit is secured in the panel. Screw Torque: 2.6~3.5 lbf.in. (For reaching waterproof effect 
and to prevent the panel from being deformed.) 

VESA 
Mounting 

There are 4 holes on back panel for locking VESA, The screw: M4 P0.7mm, length: 
shorter then 8.0mm, and screw torque: 2.6 lbf.in. 

Caution!

 

Do not over tighten mounting clamps! 

Note:

 

56

Specifications 

Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and 
panel cannot flex more than 0.010”. 

10

2.1.3 Environmental Considerations 

 

z

 

The MT-600/8000 are to be used indoors as built in displays. Make sure that the displays 
are installed correctly and that the operating limits are followed (See Specifications). 

z

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, 
vapors or dusts. 

z

 

The unit should not be installed where fast temperature variations and/or high humidity 
are present. This will cause condensation of water in the device. 

z

 

Do not install these terminals in environments where have inflammable gases. 

 

 

5

2.2 Power Connections 

Make sure that all local and national electrical standards are met when the installing the unit. 
Contact your local authorities to determine which codes apply. 

11

2.2.1 Power Requirements 

 

 

Power

 

The MT-600/8000 can be powered by DC power only. The specified voltage 
range is 

24±20%

 Volts DC. This insures compatibility with most controller 

DC systems.   

The power conditioning circuitry inside the unit is accomplished by a 
switching power supply. The peak starting current can be as high as 700mA.

 

Fusing 
Requirements

 

If the display does not come on within 5 seconds of power up, remove 
power. An internal fuse will prevent damage if the polarity of the DC power 
is incorrect. Check wiring to insure proper connections and try to power up 
again. 

 

50

Caution 

49

High Voltage

 

An Internal fuse will prevent damage for over voltage condition however it 
isn’t guaranteed. 

DC voltage sources should provide proper isolation from main AC power 
and similar hazards. 

2

 

Summary of Contents for MT-6056i

Page 1: ...s has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 1 2 0 Installation Inst...

Page 2: ...splays Make sure that the displays are installed correctly and that the operating limits are followed See Specifications z Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install these...

Page 3: ...al 1 2 2 2 2 Grounding Requirements Chassis ground must be used DC ground is not directly coupled to Earth ground internally It is preferable not to ground DC negative return to chassis ground as poor site earths can introduce noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as sho...

Page 4: ...dards To conform with ICS Safety Recommendations checks should be place in the controller to ensure that all writable registers that control critical parts of plant or machinery have limit checks built into the program wit Programming C an out of lim 3 304 81 Safety Recommendations Consid controller Where the operator is exposed to the machinery such as in loading or unloading a machine tool or wh...

Page 5: ...0 to download projects from PC by the USB 2 0 client port Support USB 2 0 client interface The cable regulation must accord with HI SPEED USB Revision 2 0 SHIELDED How to install USB driver of HMI i series It is necessary to install USB driver of HMI on PC before at the first time enjoying this function The HMI models MT6050i MT6056i MT6070iH MT6100i MT8070iH and MT8100i 1 Using USB cable mini sid...

Page 6: ...een parameter will be stored in Flash er Rom z If losing or forgetting system passwords users can set Dip Switch 1 to ON position the rest of Dips remain on OFF position and then reboot MT8000 series Under this situation MT8000 series will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired restoring the sy...

Page 7: ... misuse including but not l b imit to incorrect set up and wiring current leakage from machine platform and incorrect input power modified in any way 3 0 Specifications Hardware Specification Display 5 6 TFT LCD Brightness 300 cd m2 Color 65 s r 536 colo Contrast Ratio 300 1 Resolution WxH dots 320 x 234 Back light LED Backlight life time avg 30 000 hr min Touch panel 4 wires resistive type Touch ...

Page 8: ...Cutout dimensions MT 6056i 192mm 7 56 W x 138mm 5 43 H Front View Rear View Bottom View a DIP SW Reset button e USB Client port b Fuse f Com1 RS232 c Power connector g Com1 RS485 d VESA 75mm screw holes GME6056I0_MT6056i_Installation_101028 8 ...

Reviews: