Installation Instruction 

 

 
1.0 Installation and Startup Guide   

Install Environment 

 

Where  
Used

 

The MT-6050iV3 Series is designed for industrial. The temperature range of operating 
is from 32 to 122 °F (0 to 50 °C), as majority of industrial environments. It may not be 
suitable for using in certain outdoor applications. Please consult the factory for 
advised usage in outdoor applications. 

NEMA 

Rating 

 

The MT-6050iV3 Series front bezel is NEMA 4 rated. When installed properly in a 
NEMA 4 panel, the NEMA 4 rating of the panel will not be compromised. This means 
that fluids will not enter the panel during wash downs. 

Electrical 

Environment 

The MT-6050iV3 Series has been tested to conform to European CE requirements. 
This means that the circuitry is designed to resist the effects of electrical noise. This 
does not guarantee noise immunity in severe cases.    Proper wire routing and 
grounding will insure proper operation. 

Mechanical 

Environment 

 

 

 

 

Avoid installing units in environments where severe mechanical vibration or shocks 
are present. 

 

2.0 Installation Instructions 

2.1 Mounting Instructions 

2.1.1 Location Considerations 

 

Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC 

output modules, contactors, starters and relays, and any other source of electrical interference are located 

away from the back of the unit. 

 

Particular note should be taken to the position of variable speed drives and switching power supplies. 

Their input and load cables should be screened to a central star earth point. 

 

Summary of Contents for MT-6050iV3 Series

Page 1: ...es has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Pro...

Page 2: ...are followed See Specifications z Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts z The unit should not be installed where fast temperature variat...

Page 3: ...int to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the p...

Page 4: ...t errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufact...

Page 5: ...specific location Advanced 2 Check Include this location in the search and assign the path to install Weintek HMI i Series driver from C EB8000 usbdriver 3 If the USB driver successfully be installed...

Page 6: ...rked to indicate compliance with the EMC Directive The MT 6050iV3 Series has been designed to operate satisfactorily in electromagnetic noise immunity and without emitting high levels of electrical no...

Page 7: ...port N A USB USB Client port x 1 Processor 32bit RISC CPU 400MHz Flash memory 128MB SD card slot N A RTC N A General Specification Input Power 24 20 VDC Max Power Consumption 250 mA 24VDC Isolated Pow...

Page 8: ...Power Connector 128mm 5 039 102mm 4 016 119mm 4 685 93mm 3 661 R2mm R0 079 MT6050iV3 119mm 4 685 W x 93mm 3 661 H Front View 38 22mm 1 505 Reset DIP SW COM 117 73mm 4 635 91 53mm 3 603 FUSE5X20 a b c...

Reviews: