background image

1

 

MT-500 series 

 

MT-506T, MT-506S, 

MT-506L 

Installation Instruction 

 
 

1.0 Installation and Startup Guide   

Install Environment 

Where  
Used

 

The MT-500 Series is designed for use in a factory environment. It is designed to 
operate from 32 to 113 °F (0 to 45 °C) temperatures, as found in most industrial 
environments. It may not be suitable for use in certain outdoor applications. Please 
consult the factory for advised usage in outdoor applications. 

NEMA 
Rating 
 

The MT-500 Series front bezel is NEMA 4 rated. When installed properly in a NEMA 
4 panel, the NEMA 4 rating of the panel will not be compromised. This means that 
fluids will not enter the panel during wash downs. 

Electrical 
Environment 

The MT-500 Series has been tested to conform to European CE requirements. This 
means that the circuitry is designed to resist the effects of electrical noise. This does 
not guarantee noise immunity in severe cases.    Proper wire routing and grounding 
will insure proper operation. 

Mechanical 
Environment 

 

Avoid installing units in environments where severe mechanical vibration or shocks 
are present. 

2.0 Installation Instructions 

2.1 Mounting Instructions 

 

2.1.1 Location Considerations 

 

Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC 

output modules, contactors, starters and relays, and any other source of electrical interference are located 

away from the back of the unit. 

 

Particular note should be taken to the position of variable speed drives and switching power supplies. 

Their input and load cables should be screened to a central star earth point. 

 

2

 

2.1.2 Making a NEMA-4 Mounting 

Panel  
Details

 

The unit can be mounted into panels with a depth of 4”(105mm).    It is recommended that 
the unit be mounted on the front panel of a steel enclosure, through an appropriate 
opening*. Allow a clearance of 1”(25mm) around the sides of the unit for mounting 
hardware. Allow clearance for cable connections to the back of the unit. Unit depth may 
vary according to cable type used. Typically, plan a depth to accommodate at least 
4”(105mm) behind the panel. 

NEMA-4 
Mounting

 

Put the unit through the panel cut out. Slide the clamps into the 6 holes provided around 
the case. Tighten the clamping screws in an even pattern until the unit is secured in the 
panel. 

Caution!

 

Do not over tighten mounting clamps! 

Note:

 

Specifications 

Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and 
panel cannot flex more than 0.010”. 

2.1.3 Environmental Considerations 

 

 

The MT-500 are to be used indoors as built in displays. Make sure that the displays are 
installed correctly and that the operating limits are followed (See Specifications). 

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, 
vapors or dusts. 

 

The unit should not be installed where fast temperature variations and/or high humidity 
are present. This will cause condensation of water in the device. 

 

Do not install these terminals in environments where have inflammable gases. 

 

2.2 Power Connections 

Make sure that all local and national electrical standards are met when the installing the unit. 

Contact your local authorities to determine which codes apply. 

2.2.1 Power Requirements 

 

Power 

The MT-500 can be powered by DC power only. The specified voltage range 

is +21 to 25 Volts DC.    This insures compatibility with most controller DC 

systems.  
The power conditioning circuitry inside the unit is accomplished by a 

switching power supply. The peak starting current can be as high as 700mA. 

 

Fusing 
Requirements

 

If the display does not come on within 2 seconds of power up, remove 

power. An internal fuse will prevent damage if the polarity of the DC power 

is incorrect. Check wiring to insure proper connections and try to power up 

again. 

 

Caution 
High Voltage

 

An Internal fuse will prevent damage for over voltage condition however it 
isn’t guaranteed. 

DC voltage sources should provide proper isolation from main AC power 
and similar hazards. 

 

Caution 
Emergency Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using an 

MT-500 to comply with ICS Safety Recommendations. 

 

Caution 
Supply Voltage 
Condition 

Do not power the MT-500 and inductive DC loads, or input circuitry to the 

controller, with the same power supply. Note: The 24 VDC output from 

some controllers may not have enough current to power the MT-500. 

 

3

 

 

Caution  

Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 

1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot or 

signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 

suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 

signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 

earth ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1MOhm and 4700pF. 

 

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 

turn the connector screw counterclockwise until the gap is wide open, insert 

the wire all the way in, and turn the screw clockwise until it’s tight. 
Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 

‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

2.2.3 CE Requirements 

To make an MT-500 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 

power connector. This ground connection should be run directly to the central star earth connection 

point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

Hardware 
Considerations 

WARNING! 
The system designer should be aware that devices in Controller systems could 

fail and thereby create an unsafe condition. Furthermore, electrical 

interference in an operator interface, such as an MT-500, can lead to 

equipment start-up, which could result in property damage and/or physical 

injury to the equipment operator. 
If you, or your company, use any programmable control systems that require 

an operator or attendant, you should be aware that this potential safety hazard 

exists and take appropriate precautions. Although the specific design steps 

depend on your particular application, the following precautions generally 

apply to installation of solid-state programmable control devices. In addition, 

these precautions conform to the guidelines for installation of Controllers as 

recommended in the NEMA ICS 3-304 Control Standards. 

Programming 

Considerations 

 

To conform with ICS Safety Recommendations, checks should be placed in 

the controller to ensure that all writable registers that control critical parts 

of plant or machinery have limit checks built into the program, with an 

out-of-limit safe shut down procedure to ensure safety of personnel. 

4

 

ICS 3-304.81 Safety Recommendations: 

     

Consideration should be given to the use of an emergency stop function, which is independent of the programmable 

controller. 
      Where the operator is exposed to the machinery, such as in loading or unloading a machine tool, or where the machine 
cycles automatically, consideration should be given to the use of an electromechanical override or other redundant means, 
independent of the programmable controller, for starting and interrupting the cycle. 
      If provision is required for changing programs while the equipment is in operation, consideration should be given to the 
use of locks or other means of assuring that only authorized personnel can make such changes. 
      These recommendations are intended as safeguards against the failure of critical components and the effects of such 
failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation. * 

 

 

The ICS 3-304.81 Safety Recommendations are reproduced by permission of the National Electrical 

Manufacturers Association from NEMA ICS 3-304 

 

2.3 Communications Connections 

The ports as you look at the back of the case, are the ports for connecting to a printer, PLC or some 

external device (Controller Connectors). 

 

2.3.1 Connection to an External Device 

Cable 

Requirements 

Different cables are required for various devices. 

 

Caution 

Restrict cable length to less than 500’ (150m) for RS485/422 devices and 50’ 
(15m) for RS232 devices to avoid communications problems. 
Communications problems cause the display to show “PLC no response...” 
until communications can be established. The COM light on the front of the 
MT-500 will turn on with each communication. 

Shielded cable must be used for long lengths or cables run in an electrically 
noisy environment. 

Do not run cables next to AC power lines or near sources of electrical noise.   

Be sure that the cable ends have been inserted all of the way into mating 
connectors and are secure. 

Pin Designations 

 

PLC [RS-232]

 

Pin assignment of the 9 Pin, Female, SUB-D, PLC [RS-232] Port. This port 

is used for connecting the MT-500 to a controller.   

Note:

 This port is not used for programming the MT-500 or for printing 

functions. 

 

Pin# Symbol  PLC 

[RS232] 

AUX[RS232] 

(only E4 series) 

1 Aux_TxD 

 

 

Transmitted 

Data 

2 TxD  Transmitted 

Data   

3 RxD  Received 

Data 

 

4 Not 

used 

 

 

5 GND 

Signal 

Ground 

6 Aux_RxD 

 

Received 

Data 

CTS   

Clear to send input 

 

RTS 

Ready to send output 

 

9 +5V   

 

 

 

Reviews: